Function group 4 – digital display modes – KB Electronics KBDA-42 User Manual

Page 36

Advertising
background image

35

Function

No.

Description

Range/Code

Factory

Setting

4.00

Display Mode

0000: Frequency

0001: RPM

(1)

0002: Custom Units

0000

4.01

Custom Units Significant Digits

0 – 9999

100

4.02

Custom Units Display

0000: Whole Numbers
0001: One Decimal Place
0002: Two Decimal Places
0003: Three Decimal Places

0000

4.03

Display in Stop Mode

0000: Displays Last Run Setting
0001: Displays “StoP”
0002: Displays “0000”

0000

4.04

Motor Current Display

(2), (3)

0000: Disabled
0001: Enabled

0000

4.05

Motor Voltage Display

(2), (3)

0000: Disabled
0001: Enabled

0000

4.06

Bus Voltage Display

(2), (3)

0000: Disabled
0001: Enabled

0000

FUNCTION GROUP 4 – DIGITAL DISPLAY MODES

Notes: (1) Based on 4-pole motor. (2) The Display Key is used to toggle between displays. See Figure 22, on page 29. (3) If Motor Current

Display is enabled, the display will show “XX.XA”. If Motor Voltage Display is enabled, the display will show “XXXu”. If Bus Voltage Display is

enabled, the display will show “XXXU”.

Function

No.

Description

Range/Code

Factory

Setting

5.00

Relay Operation Mode

0000: Run

0001: Fault

(1)

0002: Target Frequency

(Function No. 5.01 ± Function No. 5.02)

0003: Frequency Threshold Level

(> Function No. 5.01 – Function No. 5.02)

(2)

0004: Frequency Threshold Level

(< Function No. 5.01 + Function No. 5.02)

(3)

0005: I2t or I•t Fault
0006: Load Loss (See Function No. 5.03)

0000

5.01

Frequency Reached (Hz)

0.00 – 240.0

0.00

5.02

Frequency Bandwidth (Hz)

0.00 – 30.00

1.00

5.03

Load Loss Threshold

(4)

(% Motor Current, set by 0.01)

25 – 90

60

FUNCTION GROUP 5 – ONBOARD MULTI-FUNCTION OUTPUT RELAY OPERATING MODE

Note: (1) The Output Relay contacts will change state due to all Faults and Recovered Faults. (2) The relay will activate above the setting in

Function No. 5.01 and deactivate below the setting in Function No. 5.01 minus the setting in Function No. 5.02. (3) The relay will activate

below the setting in Function No. 5.01 and deactivate above the setting in Function 5.01 plus the setting in Function No. 5.02. (4) The Load

Loss Threshold function is not functional during acceleration/deceleration or Stop Mode.

Advertising
This manual is related to the following products: