Start, 0 - ±5 volts dc v, Other functions and features of the ioda – KB Electronics KBDA-42 User Manual

Page 50

Advertising
background image

49

A8.

SIGNAL FOLLOWING

An analog voltage (unidirectional or bidirectional), current, or PWM signal input can be used to control

motor speed in lieu of the Keypad or the Built-In Potentiometer. The drive output will linearly follow the

signal input. The inputs can be programmed for the desired gain, slope, offset, and response time.

See Analog Input Signal Operation (Function Group 9).

Analog Input 1 – Connect the signal input to Terminal “19” and the common to Terminal “20”, as

shown in Figure 34. See settings for Analog Input 1 (Function Nos. 9.00 – 9.04). Set Frequency

Control (Function No. 2.00) to Analog Input 1 (“0002”). For unidirectional voltage input, set Analog

Input 1 Type (Function No. 9.03) to Unidirectional ((“0000”) (factory setting)). For bidirectional voltage

input, set Function No. 9.03 to Bidirectional (“0001”). See Table 14, on page 50, for Analog Input 1

electrical ratings.

If the Analog Input 1 signal is higher than 5 Volts, use Trimpot MAX1 to attenuate it. Apply the maxi-

mum signal input and set the drive for full speed output and observe the display. Rotate Trimpot

MAX1 counterclockwise until the drive output frequency begins to drop. Then rotate Trimpot MAX1

clockwise until the display returns to the maximum output frequency.

FIGURE 33 – 3-WIRE START/STOP SWITCH OR CONTACT CONNECTION AND FUNCTION SETTINGS

1

Start

15

TB1

Stop

Momentarily close the Start Switch or Contact to run the drive.
Momentarily open the Stop Switch or Contact to stop the drive.

3

2

16

17

5

4

18

19

7

6

20

21

9

8

22

23

28

11

10

24

25

13

12

27

26

14

Function Settings

Function No.

Code

1.00

Run/Stop-Forward/Reverse

Control

0001

External

Contacts

7.00

Multi-Function

Input Terminal 1

0010

Normally Open

Start

7.01

Multi-Function

Input Terminal 2

0011

Normally Closed

Stop

FIGURE 34 – ANALOG INPUT 1 SIGNAL VOLTAGE FOLLOWING CONNECTION AND FUNCTION SETTINGS

-

+

14

4

16

15

1

TB1

18

17

2

3

9

21

20

19

5

6

23

22

7

8

26

25

24

10

11

28

27

12

13

0 - ±5 Volts DC

V

MAX1

Function Settings

Function No.

Range/Code

2.00

Frequency

Control

0002

Analog

Signal 1

9.00

Analog Input 1

Gain

0 – 500

Set to the

Desired Gain

9.01

Analog Input 1

Slope

0000 or 0001

Positive or

Negative

9.02

Analog Input 1

Offset

0 – 100

Set to the

Desired Offset

9.03

Analog Input 1

Type

0000 or 0001

Unidirectional or

Bidirectional

9.04

Analog Input 1

Response Time

2 – 100

Set to the

Desired Time

OTHER FUNCTIONS AND FEATURES OF THE IODA

Advertising
This manual is related to the following products: