6.2

GROUND CONNECTION – Connect the ground wire (earth) to any available green Ground Screw.

The two Ground Screws are located near Terminal Block TB1. Be sure the motor is also properly

grounded. See Figure 10, on page 18, and Figure 11, above.

6.3

MOTOR CONNECTION – Connect the motor to Terminal Block TB1 Terminals “U”, “V”, “W”. See

Figure 10, on page 18, and Figure 11, above. Be sure the motor is properly grounded. Motor cable

length should not exceed 100 ft. (30 m) – special reactors may be required – consult our Sales

Department. Be sure Function No. 0.01 is set to the corresponding Motor Nameplate Current.

Note: If the motor does not rotate in the desired direction, either: 1. Reverse any two motor leads

(with AC line disconnected and motor stopped). or 2. Use the FWD/REV Key. or 3. Use Function

No. 1.02 to reprogram the forward and reverse direction.

6.4

MULTI-FUNCTION OUTPUT RELAY CONNECTION – The Multi-Function Output Relay Contacts

are located at TB2, as shown in Figure 12. The Multi-Function Output Relay is factory pro-

grammed to function as a “Run” relay (Function No. 5.00 set to “0000”). When the drive is put into

the Run Mode, the relay contacts will change state (the Normally Open (N.O.) contact will close

and the Normally Closed (N.C.) contact will open). See Table 5.

19

Normally Closed

Relay Common

Normally Open

Output Contacts

KBDA-27D, 29, 45, 48

NC

NO

TB2

COM

Normally Closed

Relay Common

Normally Open

Output Contacts

KBDA-24D

NC

NO

TB2

COM

Ground

3-Phase, 50/60 Hz

Motor

(Earth)

AC Line Input

V

U

L3

L2

W

L1

208/230, 400/460 Volt

TB1

MOTOR

AC LINE

Ground

Single-Phase, 50/60 Hz

(Earth)

208/230 Volt

L2

L1

L3

Wire the single-phase AC line input

to Terminals "L1" & "L2", as shown below.

Model KBDA-29 Only

AC Line Input

Notes: 1. Model KBDA-29 is rated for 2 HP maximum with single-phase AC line input and 3 HP maximum with 3-phase AC line input.

2. Models KBDA-29, 45, 48 contain AC Line Phase Loss Detection. (Model KBDA-29: when used on 3-phase AC line input set for 7.0 Amps

or higher (3 HP (2.25 kW)).

FIGURE 11 – MODELS KBDA-29

1

, 45

2

, 48

2

AC LINE INPUT, MOTOR, AND GROUND CONNECTIONS

FIGURE 12 – MULTI-FUNCTION OUTPUT RELAY CONTACTS

TABLE 5 – MULTI-FUNCTION OUTPUT RELAY “RUN” AND “FAULT” RELAY OPERATING MODES

Drive Operating Condition

Function 5.00 Set to “0000”

Function 5.00 Set to “0001”

“Run” Relay Mode

“Fault” Relay Mode

N.O. Contact

N.C. Contact

N.O. Contact

N.C. Contact

Power Off

Open

Closed

Open

Closed

Power On (Stop Mode)

Open

Closed

Closed

Open

Run Mode

Closed

Open

Closed

Open

All Faults

Open

Closed

Open

Closed