KB Electronics KBDA-42 User Manual

Page 38

Advertising
background image

37

Function

No.

Description

Range/Code

Factory

Setting

8.00*

Multi-Function Output Relay 1
(Terms. 23 – 25)

0000: Run

0001: Fault

(1)

0002: Target Frequency

(Function No. 8.04 ± Function No. 8.05)

0003: Frequency Threshold Level

(> Function No. 8.04 – Function No. 8.05)

(2)

0004: Frequency Threshold Level

(< Function No. 8.04 + Function No. 8.05)

(3)

0005: I2t or I•t Fault

0006: Load Loss (See Function No. 5.03)

0007: External Fault

0008: Motor Overload

(4)

0000

8.01*

Multi-Function Output Relay 2
(Terms. 26 – 28)

0001

8.02*

Multi-Function Open Collector Output 1
(Terms. 11, 12)

0002

8.03*

Multi-Function Open Collector Output 2
(Terms. 13, 14)

0004

8.04

*

Frequency Set Point (Hz)

0.00 – 240.0

0.00

8.05

*

Frequency Bandwidth (± Hz)

0.00 – 30.00

1.00

8.06

*

Analog Output 1 Mode (Terms. 15, 16)
(0 – 5 VDC)

0000: Motor Frequency

0001: Set Frequency

0002: Motor Voltage

0003: Bus Voltage

0004: Motor Current

0000

8.07

*

Analog Output 1 Gain (%)

0 – 200

100

8.08

*

Analog Output 2 Mode (Terms. 17, 18)
(See Function No. 8.09)

0000: Motor Frequency

0001: Set Frequency

0002: Motor Voltage

0003: Bus Voltage

0004: Motor Current

0000

8.09

*

Analog Output 2 Type

(5)

0000: 0 – 5 VDC

0001: 0 – 20 mA DC

0002: 4 – 20 mA DC

0000

8.10

*

Analog Output 2 Gain (%)

0 – 200

100

FUNCTION GROUP 8 – MULTI-FUNCTION OUTPUT RELAYS AND
OUTPUT SIGNAL OPERATION (IODA OPTION BOARD REQUIRED)

Notes: (1) The Multi-Function Output Relays and Open Collector Outputs will change state due to all Faults and Recovered Faults. (2) The

relay will activate above the setting in 8.04 and deactivate below the setting of 8.04 – 8.05. (3) The relay will activate below the setting in

8.04 and deactivate above the setting of 8.04 + 8.05. (4) The Output Relay will change state when the I

2

t or I•t Timer starts. (5) Analog

Output 2 Type: For 0 – 5 VDC (code “0000”), set Jumpers J2 and J3, on the IODA, to the “VOLT” Position (factory setting). For 0 – 20 mA DC

(code “0001”) or 4 – 20 mA DC (code “0002”), set Jumpers J2 and J3, on the IODA, to the “CUR” position.

*Functions which can only be changed while the drive is in the Stop Mode.