LEESON SM-Basic Series Sub-Micro Inverters (Obsolete) User Manual

Page 18

Advertising
background image

14

11.2

THREE-WIRE START/STOP CONTROL

NOTES:

1.

Program TB-13C (Parameter 12) for START FORWARD (05).

2.

If reverse direction is required, set ROTATION (Parameter 17) to FORWARD AND REVERSE
(02), and program TB-13A (Parameter 10) for START REVERSE (06).

3.

Momentarily close TB-13C to TB-11 to START in the forward direction, or close TB-13A to
TB-11 to START in the reverse direction. Momentarily open TB-1 to TB-11 to STOP the drive.

4.

For speed pot control, set STANDARD SPEED SOURCE (Parameter 05) to SPEED POT (03).

STOP

SPEED POT COMMON

SPEED POT INPUT

SPEED POT POWER SUPPLY

TB-13A FUNCTION SELECT

(START REVERSE)

TB-13B FUNCTION SELECT

TB-13C FUNCTION SELECT

(START FORWARD)

OPEN-COLLECTOR OUTPUT

DIGITAL INPUT REFERENCE

MOMENTARY

STOP CONTACT

SPEED

POT

MOMENTARY

START CONTACT

REV

FWD

1

3

5

6

11

13A

13B

14

13C

WARNING!

Hazard of electrical shock! The SM-Basic control terminals are not isolated from line voltage!
Line voltage is present between the control terminals and ground. Do not touch!

Disconnect input power and wait three minutes before making connections to the control terminals.

Devices (such as switches, pushbuttons, potentiometers, relays, etc) and wiring connected to the
control terminals are hot to ground and must have an insulation rating of at least 240 Vac or a
dielectric rating of at least 1500 volts to prevent damage to equipment and/or injury to personnel.