Advertising
background image

3

Protect the drive from dirt, moisture, and accidental
contact.

Provide sufficient room for access to the terminal block
and calibration trimpots.

Mount the drive away from heat sources. Operate the
drive within the specified ambient operating temperature
range.

Prevent loose connections by avoiding excessive
vibration of the drive.

Mount drive with its board in either a horizontal or vertical
plane. Six 0.19 in. (5 mm) wide slots in the chassis
accept #8 pan head screws. Fasten either the large
base or the narrow flange of the chassis to the subplate.

The chassis must be earth grounded. Use a star washer

beneath the head of at least one of the mounting screws
to penetrate the anodized chassis surface and reach
bare metal.