Installation

SPEEDMASTER™ OPERATION MANUAL

SO501

INHIBIT

MIN SPD

ACCEL

T501

O

V502

R502

C503

SW501

230 - 115

TQ LIMIT

IR COMP

DECEL

MAX SPD

SO502

S3 S2 S1

SW502

180 - 90

IC502

C501

C504

R501

MAX ARMATURE VOLTAGE SWITCH

SW502 (90 or 180 VDC)

AC LINE VOLTAGE SWITCH

SW501 (115 or 230 VAC)

Figure 4. Voltage Switches

Voltage Switches

• Set voltage switch SW501 to either 115 or 230 to match the

AC line voltage (see Figure 4 below).

• Set voltage switch SW502 to either 90 or 180 to match the

maximum armature voltage (see Figure 4 below).

Field Output

The field output is for shunt wound motors only. Do not make
any connections to F1 and F2 when using a permanent magnet
motor. Use 18 AWG wire to connect the field output to a shunt
wound motor. Table 2 lists the field output connections.

Table 2. Field Output Connections

Line Voltage

Approx. Field

Connect Motor

(VAC)

Voltage (VDC)

Field To

115

50

F1 and L1

115

100

F1 and F2

230

100

F1 and L1

230

200

F1 and F2