Symptom possible causes suggested solutions – LEESON NEMA 4X SCR Control: 174107.00 User Manual

Page 43

Advertising
background image

37

Troubleshooting

SPEEDMASTER™ OPERATION MANUAL

Symptom

Possible

Causes

Suggested

Solutions

Line fuse does not
blow or circuit
breaker does not
trip, but the motor
does not run (cont.)

Motor runs too fast
at maximum speed
setting

Motor runs too slow
or too fast

Motor will not reach
the desired speed.

3. Drive is in current

limit.

4. Drive is not receiving

AC line voltage.

5. Motor is not

connected.

1. MIN SPD and MAX

SPD settings are too
high.

1. MIN SPD and MAX

SPD are not
calibrated.

1. MAX SPD setting is

too low.

2. IR COMP setting is

too low.

3. Motor is overloaded.

3. Verify that the motor

is not jammed.
Increase TORQUE
setting (page 14).

4. Apply AC line

voltage to L1 and L2.

5. Connect motor to A1

and A2.

1. Recalibrate MIN

SPD (page 12) and
MAX SPD (page
13).

1. Recalibrate MIN

SPD (page 12) and
MAX SPD (page
13).

1. Increase MAX SPD

setting (page 13).

2. Increase IR COMP

setting (page 13).

3. Check motor load.

Resize the motor or
drive if necessary.