Installation

Shielding guidelines

As a general rule, LEESON recommends shielding of all

conductors.

If it is not practical to shield power conductors, LEESON

recommends shielding all logic-level leads. If shielding of logic level

leads is not practical, the user should twist all logic leads with

themselves to minimize induced noise.

It may be necessary to earth ground the shielded cable. If noise is

produced by devices other than the drive, ground the shield at the

drive end. If noise is generated by a device on the drive, ground

the shield at the end away from the drive. Do not ground both ends

of the shield.

If the drive continues to pick up noise after grounding the shield

mount the drive in a less noisy environment.

Logic wires from other input devices, such as motion controllers

and PLL velocity controllers, must be separated from power lines in

the same manner as the logic I/O on this drive.

Warning

Under no circumstances should power and logic leads be
bundled together. Induced voltage can cause unpredictable
behavior in any electronic device, including motor controls.