Water system piping, Piping installation – American Water Heater 317994-002 User Manual

Page 15

Advertising
background image

15

Piping Installation

Piping, fittings, and valves should be installed according

to the installation drawing (Figure 13). If the indoor

installation area is subject to freezing temperatures, the

water piping must be protected by insulation.
The water supply pressure should not exceed 80 psi. If

this occurs, a pressure reducing valve with a bypass may

need to be installed in the cold water inlet line. This should

be placed on the supply to the entire house in order to

maintain equal hot and cold water pressures.
IMPORTANT: Heat cannot be applied to the water fittings

on the heater as they may contain nonmetallic parts. If

solder connections are used, solder the pipe to the adapter

before attaching the adapter to the hot and cold water

fittings.
IMPORTANT: Always use a good grade of joint compound

and be certain that all fittings are drawn up tight.
1. Install the water piping and fittings as shown in Figure

13. Connect the cold water supply (3/4” NPT) to the

cold water inlet fitting. Connect the hot water piping

(3/4” NPT) to the hot water outlet fitting.

IMPORTANT: Some models may contain energy saving

heat traps to prevent the circulation of hot water within the

pipes. Do not remove the inserts within the heat traps.
2. The installation of unions in both the hot and cold water

supply lines is recommended for ease of removing the

water heater for service or replacement.

3. The manufacturer of this water heater recommends

installing a mixing valve or an anti-scald device in the

domestic hot water line as shown in Figure 14. These

valves reduce the point-of-use temperature of the

water by mixing cold and hot water and are readily

available for use.

4. If installing the water heater in a closed water system,

install an expansion tank in the cold water line as

specified under Closed System/Thermal Expansion.

5. Install a shut-off valve in the cold water inlet line. It

should be located close to the water heater and be

easily accessible. Know the location of this valve and

how to shut off the water to the heater.

6. A temperature and pressure relief valve must be

installed in the opening marked “Temperature and

Pressure (T & P) Relief Valve” on the water heater.

A discharge line must be added to the opening of

the T&P Relief Valve. Follow the instructions under

Temperature and Pressure Relief Valve.

7. After piping has been properly connected to the water

heater, remove the aerator at the nearest hot water

faucet. Open the hot water faucet and allow the tank

to completely fill with water. To purge the lines of

any excess air, keep the hot water faucet open for

3 minutes after a constant flow of water is obtained.

Close the faucet and check all connections for leaks.

WATER SYSTEM PIPING

Maintain

Clearance*

Support Strap

3 FT.

Minimum

Vent

Connector

Slope Up

1/4 Inch

Per Foot

Minimum

**Maintain

Specified

Clearance

Venting Gas Vent System With Type B Double Wall Vent Pipe.

2 FT. Minimum Above

Any Object Within

10 FT. Horizontally

Type B Double
Wall Vent Pipe

FIGURE 11.

Seal

Maintain

Clearance*

Support Strap

Specified Minimum Clearance

Vent

Connector

Slope Up

1/4 Inch

Per Foot

Minimum

Vent Connector

**Maintain

Specified

Clearance

Venting Through Chimney With Type B Double Wall Vent Pipe.

Unused Chimney

Flue Or Masonry

Enclosure

Maintain Manufacturer’s

Listed Vent Cap

FIGURE 12.

*

Maintain vent pipe clearance requirements to local, state

and/or the “National Fuel Gas Code”, ANSI Z223.1(NFPA

54)-current edition.

**

NFPA 211, Standard for Chimneys, Fireplaces, Vents, and

Solid Fuel-Burning Appliances states that these chimneys are
intended to be installed in accordance with the installation
instructions provided with each chimney support assembly.
Minimum air space clearance to combustible materials should be
maintained as marked on the chimney sections.

Advertising