This device has snubber circuits designed to protect the contacts of the
mechanical relays when it switches to inductive loads (i.e. solenoids, relays).
These snubbers are internally connected between the Common (C) and
Normally Open (NO) relay contacts of Output 1 and Output 2.

If you have an inductive load connected between Common (C) and
Normally Closed (NC) contacts of the mechanical relays and you want to
protect them from the rush current during the switching period, you have
to connect an external snubber circuit between Common (C) and
Normally Closed (NC) contacts as indicated in the figure below.

Figure 2.10 Snubber Circuits Wiring Hookup

Figure 2.11 Typical Applications

TEMPERATURE

CONTROLLER

CONTROL

SIDE

dc INPUT

SSR

ac INPUT

SSR

ac INPUT

SSR

LOAD

SIDE

HEATER

Vac

Vac

dc CONTROLLED SSR USED WITH TEMPERATURE CONTROLLER WITH dc VOLTAGE SSR DRIVER OUTPUT

FAST BLOW

FUSE

0 or 5 Vdc,

TYPICALLY

4

3

1

2

TEMPERATURE

CONTROLLER

CONTROL

SIDE

LOAD

SIDE

HEATER

Vac

Vac

ac CONTROLLED SSR USED WITH TEMPERATURE CONTROLLER WITH MECHANICAL RELAY OUTPUT

FAST BLOW

FUSE

Vac

DRIVING

SSR

4

3

1

2

TEMPERATURE

CONTROLLER

CONTROL SIDE

LOAD

RESISTOR

LOAD

SIDE

HEATER

Vac

Vac

ac CONTROLLED SSR USED WITH TEMPERATURE CONTROLLER WITH TRIAC OUTPUT

FAST BLOW

FUSE

Vac

DRIVING

SSR

4

3

1

2

RC CIRCUIT

OR

VARISTOR

275 V

C

NC

NO

C

NC

NO

OUTPUT 1 OUTPUT 2

100

1/4 W

0.033

12

Advertising