NEWPORT iDRA Controller User Manual

Page 35

Advertising
background image

31

READING ADJUST SUBMENU:

Press

d

10) Display flashes 1

st

digit of previous reading adjust value.

Press

b & c 11) Press b and c buttons to enter a new Reading Adjust value

(-1999 to 9999).

Press

d

12) Display shows

STRD stored message momentarily and then

advances to

SP.DV Setpoint Deviation Menu.

Reading Offset Adjust allows the user to fine tune a minor error of the transducer,
however some applications may require a large offset adjust.
(Displayed Process Value = Measured Process Value ± R.ADJ).
Reading Adjust is adjustable between -1999 to 9999. For Temperature reading only, not
Process.

SETPOINT DEVIATION ENABLE/DISABLE SUBMENU:

Press

d

13) Display advances to Setpoint Deviation

ENBL Enable or

DSBL Disable Submenu and flashes the previous selection.

Press

b

14) Scroll through the available selections:

ENBL or DSBL.

Press

d

15) Display shows

STRD stored message momentarily and then

advances to the

CAL1 Menu.

Setpoint Deviation Submenu, if “enabled”, allows changes to Setpoint 1 to be made
automatically to Setpoint 2. This mode is very helpful if the Process Value changes often.
In Setpoint Deviation Mode, set SP2 a certain number of degrees or counts away from
SP1 - this relation remains fixed when SP1 is changed. For instance: Setting SP1=200
and SP2=20 and enabling

SP.DV means that the absolute value of SP2=20. Moving SP1

to 300, the absolute value of SP2 becomes 320.

THERMOCOUPLE FIELD CALIBRATION SUBMENU:

RTD and Process are perfectly calibrated. This section is applicable to
Thermocouple (TC) calibration only.

Be sure that the TC being used to calibrate the meter is of the type
selected in the TC submenu. Place the TC in an ice-bath (or other
0°C / 32°F environment). In ambient temperature conditions: connect the
TC to the meter, apply power to the meter.

CAUTION: Do not proceed with TC calibration unless the above conditions
have been in effect for at least one hour.

Press

a

16) Display shows

CAL1 .

Press

d

17) Display shows flashing

0000 .

Press

a

18) Display will still show flashing

0000 .

Press

d

19) Display shows

OUT1 (meaning Calibration is complete)

*

If you accidently engage the flashing

0000 (CAL° alert) simply re-press

the last button you pressed, to avoid unintentionally mis-calibrating your meter.

°°

CAUTION: Do not perform the following steps until you fully
understand this entire section.

°°