NEWPORT iDRA Controller User Manual
Page 25

21
Input Type (Process)
ENTER INPUT TYPE MENU:
Press
a
1) Press
a, if necessary, until CNFG prompt appears.
Press
d
2) Display advance to
INPT Input Menu.
Press
d
3) Display flashes
T.ç, RTD or PROC (Thermocouple, RTD or
Process). If the displayed input type is
PROC, press a to skip to
step 6 (
PROC stops flashing).
PROCESS SUBMENU:
Press
b
4) Scroll through the available selection to
PROC (flashing).
Press
d
5) Display shows
STRD stored message momentarily and then
PROC (not flashing).
Press
d
6) Display flashes previous Process type selection. i.e.
0-10
(see below for Process types selection).
Press
b
7) Scroll through the available Process types to the selection of
your choice.
Press
d
8) Display shows
STRD stored message and then advances to
RDG Reading Configuration Menu.
Process Types: 100 mV 1 V
10 V
0 – 20 mA
Display:
0-0.1
0-1.0
0-10
0-20
For 4-20 mA Input select 0-20 mA and adjust the Input/Reading accordingly.
To adjust 4-20 mA input, see example under Input/Reading Submenu.
3.2.5 Reading Configuration Menu
Figure 3.4 Flow Chart for Reading Configuration Menu
It
is required that you put the controller in the Standby Mode for any
configuration change other than Set Points & Alarms.