EXCITATION
24 Vdc @ 25 mA
Not available for:
Low Power Option (-DC) or
Serial Communication Option (-C24)

INSULATION
Power to Input/Output

2300 Vac per 1 min. test
1500 Vac per 1 min. test
(Low Voltage/Power Option)

Power to Relays/SSR Outputs

2300 Vac per 1 min. test

Relays/SSR to Relay/SSR Outputs

2300 Vac per 1 min. test

RS-232/485 to Inputs/Outputs

500 Vac per 1 min. test

Approvals
FM, UL, C-UL, and
see CE Approval Section

GENERAL

Line Voltage/Power
90-240 Vac +/-10%, 50-400 Hz*
110-375 Vdc, equivalent voltage
5 W, power consumption

* No CE compliance above 60 Hz

Low Voltage/Power Option
20-36 Vdc, 4 W**, power consumption
External power source must meet
Safety Agency Approvals.

** Units can be powered safely with 24 Vac

but, no Certification for CE/UL are claimed.

External Fuse Required
Time-Delay, UL 248-14 listed:

100 mA/250 V
400 mA/250 V

(Low Voltage/Power Option)

Time-Lag, IEC 127-3 recognized:

100 mA/250 V
400 mA/250 V

(Low Voltage/Power Option)

Environmental Conditions
0 to 55°C (32 to 131°F),
90% RH non-condensing
0 to 50°C (32 to 122°F) for UL only.
90% RH non-condensing

Dimensions iDRA
92.5H x 125.2D x 32.1 mm W
(3.64 x 4.93 x 1.27")
204g (0.45lb)

Optional Remote Programmer iDRP:
48H x 96x 39 mm D
(1.89 x 3.78 x 1.55")
159g (0.35lb)

1/8 DIN Panel Cutout
Optional Remote Programmer iDRP:
45 H x 92 mm W
(1.772" x 3.622 ")