Chapter 7: Specifications
Watlow Anafaze
99
Table 7.12
Pulse Inputs
Table 7.13
Thermocouple Range and
Resolution
* True for 10% to 100% of span except type B, which is
specified for 800°F to 3200°F.
Parameter
Description
Number
1
Frequency Range
0-2000Hz
Input Voltage Protection
Diodes to supply and common
Voltage Levels
<1.3 V = Low
>3.7 V = High (TTL)
Maximum Switch Resistance to
Pull Input Low
2k
Ω
Minimum Switch Off Resistance
30k
Ω
Thermocouple
Type
Range in °F
Range in °C
Accuracy* at
25°C Ambient
Accuracy* at
0-50°C Ambient
°
F
°
C
°
F
°
C
J
-350 to 1400
-212 to 760
±2.2
±1.2
±3.3
±1.8
K
-450 to 2500
-268 to 1371
±2.4
±1.3
±3.8
±2.1
T
-450 to 750
-268 to 399
±2.9
±1.6
±5.8
±3.2
S
0 to 3200
-18 to 1760
±5.0
±2.8
±8.8
±4.9
R
0 to 3210
-18 to 1766
±5.0
±2.8
±8.8
±4.9
B
150 to 3200
66 to 1760
±7.2
±4.0
±22.1
±12.3
E
-328 to 1448
-200 to 787
±1.8
±1.0
±2.9
±1.6
N
-450 to 2370
-268 to 1299
±2.7
±1.5
±5.0
±2.8
PL-II
50 to 2012
10 to 1100
±1.9
±1.0
±3.1
±1.7