Page 96
Advertising

Chapter 5: Troubleshooting and Reconfiguring
CAS200 User’s Guide
84
Watlow Anafaze
Table 5.4
Resistor Locations for CAS200
Current Inputs
CAS200 Voltage Inputs
For each voltage input on a CAS200 scanner, you must
install two resistors. The resistance must be correct for the
expected input range. Install the resistors in the listed
locations.
Table 5.5
Resistor Values for CAS200
Voltage Inputs
Resistor tolerance:
±
0.1%
Channel
Resistor
Location
RD
Channel
Resistor
Location
RD
1
R42
9
R41
2
R40
10
R39
3
R38
11
R37
4
R36
12
R35
5
R34
13
R33
6
R32
14
R31
7
R30
15
R29
8
R28
16
R27
Input Range
Resistor Values
RC
RD
0 - 100mVdc
499
Ω
750
Ω
0 - 500mVdc
5.49k
Ω
750
Ω
0 - Vdc
6.91k
Ω
422.0
Ω
0 - 5Vdc
39.2k
Ω
475.0
Ω
0 - 10Vdc
49.9k
Ω
301.0
Ω
0 - 12Vdc
84.5k
Ω
422.0
Ω