Watlow CAS200 User Manual
Page 114

Chapter 7: Specifications
CAS200 User’s Guide
102
Watlow Anafaze
Table 7.18
5Vdc Output (Power to Operate
Solid State Relays)
Table 7.19
Reference Voltage Output (Power
to Operate Bridge Circuit Sensors)
Table 7.20
Processor Serial Interface
Table 7.21
Processor Power Requirements
Parameter
Description
Voltage
5Vdc
Maximum Current
350mA
Parameter
Description
Voltage
5Vdc
Maximum Current
100mA
Parameter
Description
Type
EIA/TIA-232 3-wire or EIA/TIA-485 4-wire
Isolation
None
Baud Rate
2400, 9600 or 19200, user selectable
Error Check
BCC or CRC, user selectable
Number of Scanners
1 with EIA/TIA-232 communications; up to 32 with EIA/
TIA-485 communications, depending upon protocol
Protocol
Form of ANSI X3.28-1976 (D1, F1), compatible with
Allen Bradley PLC, full duplex, or Modbus RTU
Parameter
Description
Voltage
15-24Vdc (±3Vdc)
Maximum Current
1A