Output function, Watlow ez-zone, Rml module – Watlow EZ-ZONE RM Limit Module Rev C User Manual

Page 106: Chapter 6 features

Advertising
background image

Watlow EZ-ZONE

®

RML Module

103

Chapter 6 Features

Math

Sample and Hold

Range Low

Range High

Pressure Units

Altitude Units

Scale Low

Scale High

Function

Filter Offset

Filter

If E = OFF, Output Value = Filter [A + Offset]

If E = ON, Output Value = Filter [last value

of A + Offset]

Display units follows Source A

Source Function A

Source Instance A

Source Zone A

Source Error A

Source Function B

Source Instance B

Source Zone B

Source Error B

Source Function C

Source Instance C

Source Zone C

Source Error C

Source Function D

Source Instance D

Source Zone D

Source Error D

Source Function E

Source Instance E

Source Zone E

Source Error E

Source Value A

Source Value B
Source Value C

Source Value D

Source Value E

Output Value

Error

Math

Dewpoint

Range Low

Range High

Pressure Units

Altitude Units

Scale Low

Scale High

Function

Filter Offset

Filter

Output Value = Filter [427.26 * (CP *

B / 8.8618)

/ (17.27- (CP * B / 8.8618)) + 32 +

Offset]

Source A is used for Calculated

Pressure or CP ;

Note: For dewpoint, Source A is

temperature (F) and Source B is RH

(%). Saturation pressure calculation is

identical to that used in wet/dry

bulb. Result is in degrees F.

Source Function A

Source Instance A

Source Zone A

Source Error A

Source Function B

Source Instance B

Source Zone B

Source Error B

Source Function C

Source Instance C

Source Zone C

Source Error C

Source Function D

Source Instance D

Source Zone D

Source Error D

Source Function E

Source Instance E

Source Zone E

Source Error E

Source Value A
Source Value B

Source Value C

Source Value D

Source Value E

Output Value

Error

Output Function

This function configures and connects physical outputs to
internal functions.

Note:

Digital Outputs not included on these sheets

An error, when read, can indicate any of the following:
None, Open, Shorted, Measurement Error, Bad Cal Data,
Ambient Error, RTD Error, Fail, Math Error, Not Sourced,
Stale

Output

Overview

Instances - 0 to 8 per RML

Output Value

Error

Output Low P

ower Scale

Output

Time Base

Output Control

Output

High P

ower Scale

Output Function

Output Function Instance

Output Source Zone

Output Source Error

[``o;u]

Output Value : On, Off

[``Fn]

Output Function : Off, Alarm, Compare, Counter, Digital I/O,

Function Key, Linearization, Logic, Math, Timer, Variable, Limit

[`o;Ct]

Output Control : Fixed Time Base

[``Fi]

Output Function Instance : 1 to 250

[`o;Lo]

Output Low Power Scale : 0 to 100 %

[`o;hi]

Output High Power Scale : 0 to 100 %

[`o;tb]

Output Time Base : 0.1 to 60.0 seconds

[``S2]

Output Source Zone : 0 to 16

[otPt]

Output Menu

[`SEt]

Setup Page

[``o;u]

Output Value : 0 to 10.0 volts or 0 to 20.00 milliamperes

Advertising