Watlow EZ-ZONE RM Limit Module Rev C User Manual

Page 121

Advertising
background image

Watlow EZ-ZONE

®

RML Module

118

Appendix

Operating Range

Input Type

Range Low

Range High

Units

J

-210

1200

Deg C

K

-270

1371

Deg C

T

-270

400

Deg C

N

-270

1300

Deg C

E

-270

1000

Deg C

R

-50

1767

Deg C

S

-50

1767

Deg C

B

-50

1816

Deg C

C

0

2315

Deg C

D

0

2315

Deg C

F (PTII)

0

1343

Deg C

RTD (100 ohm)

-200

800

Deg C

RTD (1000 ohm)

-200

800

Deg C

mV

0

50

mV

Volts

0

10

Volts

mAdc

0

20

mAmps DC

mAac

0

50

mAmps AC

Resistance, 5K

range

0

5000

Ohms

Resistance, 10K

range

0

10000

Ohms

Resistance, 20K

range

0

20000

Ohms

Resistance, 40K

range

0

40000

Ohms

Resistance, 40K

range

0

40000

Ohms

Thermistor Input

Input

Type

Max Error

@ 25 Deg C

Accuracy

Range

Low

Accuracy

Range

High

Units

Thermis-

tor, 5K

range

±5

0

5000

Ohms

Thermis-

tor, 10K

range

±10

0

10000

Ohms

Thermis-

tor, 20K

range

±20

0

20000

Ohms

Thermis-

tor, 40K

range

±40

0

40000

Ohms

• 0 to 40KΩ, 0 to 20KΩ, 0 to 10KΩ, 0 to 5KΩ
• 2.252KΩ and 10KΩ base at 25°C
• Linearization curves built in
• Third party Thermistor compatibility requirements

Base R

@ 25C

Alpha Tech-

niques

Beta

THERM

YSI

Thermistor

Curve

2.252K

Curve A

2.2K3A

004

A

10K

Curve A

10K3A

016

B

10K

Curve C

10K4A

006

C

Digital Input

• Update rate 10Hz
• DC voltage
- Max. input 36V at 3mA
- Min. high state 3V at 0.25mA
- Max. low state 2V

Dry Contact

• Update rate 10Hz
• Min. open resistance 10KΩ
• Max. closed resistance 50Ω

Output Hardware

• Electromechanical relay, Form A, 24 to 240VAC or 30VDC max.,

5A resistive load, 100,000 cycles at rated load, 120/240 @ 125 VA

or 24VAC @ 25VA pilot duty

• Electromechanical relay, Form C, 24 to 240VAC or 30VDC max.,

5A resistive load, 100,000 cycles at rated load, 120/240 @ 125 VA

or 24VAC @ 25VA pilot duty

• Digital outputs
- Update rate 10Hz
- Switched DC
- Output voltage 20VÎ (dc)
- Max. supply current source 40mA at 20VÎ (dc) and 80mA at
12VÎ (dc)
- Open Collector
- Switched voltage max.: 32VÎ (dc)
- Max. switched current per output: 1.5A
- Max. switched current for all 6 outputs combined: 8A
• 0 to 10VÎ (dc) into a min. 1,000Ω load
• 0 to 20mA into max. 800Ω load

Programmable Application Blocks

Actions (events) 16 total
Alarms 16 total
Limit Loops 12 total
Compare 16 total
Off, greater than, less than, equal, not equal, greater than or

equal, less than or equal

Counters 16 total
Counts up or down loads, predetermined value on load signal.

Output is active when count value equals predetermined target

value

Logic 16 total
Off, and, nand, or, nor, equal, not equal, Latch
Linearization 16 total
Interpolated or stepped relationship
Math 16 total
Off, average, process scale, deviation scale, differential (subtrac-

tion), ratio (divide), add, multiply, absolute difference, min.,

max., square root, sample and hold

Timers 16 total
On Pulse produces output of fixed time on active edge of timer

run signal

Delay output is a delayed start of timer run, off at same time
One Shot oven timer
Retentive measures timer run signal, output on when accumu-

lated time exceeds target

Variable 16 total
User value for digital or analog variable

Note:

These specifications are subject to change without

prior notice.

Advertising