Watlow EZ-ZONE

®

RML Module

50

Chapter 4 Setup Page

RM Limit Module

Setup Page

Display

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Profibus

Index

Parameter

ID

Data

Type

&

Read/

Write

[`A;Sd]
[ A.Sd]

Alarm (1 to 16)

Sides

Select which side or sides

will trigger this alarm.

[both]

Both (13)

[high]

High (37)

[LoW]

Low (53)

Both

2536

[offset 60]

0x6D

(109)

1 to 0x10

(16)

4

26

9004

uint
RWES

[`A;Lo]
[ A.Lo]

Alarm (1 to 16)

Low Set Point

If Alarm Type (Setup

Page, Alarm Menu) is

set to:

process - set the process

value that will trigger a

low alarm.

-1,999.000 to 9,999.000°F or

units

-1,128.000 to 5,537.000°C

32.0°F

or units

0.0°C

- - - -

- - - -

- - - -

- - - -

- - - -

[`A;hi]
[ A.hi]

Alarm (1 to 16)

High Set Point

If Alarm Type (Setup

Page, Alarm Menu) is

set to:

process - set the process

value that will trigger a

high alarm.

-1,999.000 to 9,999.000°F or

units

-1,128.000 to 5,537.000°C

300.0°F

or units

150.0°C

- - - -

- - - -

- - - -

- - - -

- - - -

[`A;LA]
[ A.LA]

Alarm (1 to 16)

Latching

Turn alarm latching on or

off. A latched alarm has to

be turned off by the user.

[nLAt]

Non-Latching (60)

[`LAt]

Latching (49)

Non-

Latching

2542

[offset 60]

0x6D

(109)

1 to 0x10

(16)

7

27

9007

uint
RWES

[`A;bL]
[ A.bL]

Alarm (1 to 16)

Blocking

Select when an alarm will

be blocked. After startup

and/or after the set point

changes, the alarm will be

blocked until the process

value enters the normal

range.

[`oFF]

Off (62)

[`Str]

Startup (88)

[StPt]

Set Point (85)

[both]

Both (13)

Off

2544

[offset 60]

0x6D

(109)

1 to 0x10

(16)

8

28

9008

uint
RWES

[`A;Si]
[ A.Si]

Alarm (1 to 16)

Silencing

Turn alarm silencing on to

allow the user to disable

this alarm.

[`oFF]

Off (62)

[``on]

On (63)

Off

2540

[offset 60]

0x6D

(109)

1 to 0x10

(16)

6

29

9006

uint
RWES

[A;dSP]
[A.dSP]

Alarm (1 to 16)

Display

Display an alarm message

when an alarm is active.

[`oFF]

Off (62)

[``on]

On (63)

On

2560

[offset 60]

0x6D

(109)

1 to 0x10

(16)

0x10 (16)

30

9016

uint
RWES

[`A;dL]
[ A.dL]

Alarm (1 to 16)

Delay

Set the span of time that

the alarm will be delayed

after the process value ex-

ceeds the alarm set point.

0 to 9,999 seconds

0

2570

[offset 60]

0x6D

(109)

1 to 0x10

(16)

0x15 (21)

31

9021

uint
RWES

[A;Clr]
[ A.hi]

Alarm (1 to 16)

Clear Request

Write to this register to

clear an alarm

Clear

Ignore

Ignore

- - - -

- - - -

- - - -

- - - -

- - - -

Note: Some values will be rounded off to fit in the four-character display .
Full values can be read with other interfaces .

If there is only one instance of a menu, no submenus will appear .

R: Read

W: Write

E:

EEPROM

S:

User

Set