Display

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Profibus

Index

Parameter

ID

Data

Type

&

Read/

Write

[`P;EL]
[ P.EL]

Analog Input (1 to 12)

Process Error Low

If the process value drops

below this value, it will

trigger an input error.

-100.0 to 1,000.0

0.0

470
[offset 90]

0x68 (104)

1 to 0xC

(12)

0x1F (31)

11

4031

float
RWES

[``t;C]
[ t.C]

Analog Input (1 to 12)

Thermistor Curve

Select a curve to apply to

the thermistor input.

[```A]

Curve A (1451)

[```b]

Curve B (1452)

[```C]

Curve C (1453)

[CUSt]

Custom (180)

Curve A

484
[offset 90]

0x68 (104)

1 to 0xC

(12)

0x26 (38)

- - - -

4038

uint
RWES

[``r;r]
[ r.r]

Analog Input (1 to 12)

Resistance Range

Set the maximum resis-

tance of the thermistor

input.

[```5]

5K (1448)

[``10]

10K (1360)

[``20]

20K (1361)

[``40]

40K (1449)

40K

432
[offset 90]

0x68 (104)

1 to 0xC

(12)

0x25 (37)

- - - -

4037

uint
RWES

[`FiL]
[ FiL]

Analog Input (1 to 12)

Filter

Filtering smooths out the

process signal to both the

display and the input. In-

crease the time to increase

filtering.

0.0 to 60.0 seconds

0.5

386
[offset 90]

0x68 (104)

1 to 0xC

(12)

0xE (14)

12

4014

float
RWES

[`i;Er]
[ i.Er]

Analog Input (1 to 12)

Error Latching

Turn input error latching

on or off. If latching is on,

errors must be manually

cleared.

[`off]

Off (62)

[``on]

On (63)

Off

414
[offset 90]

0x68 (104)

1 to 0xC

(12)

0x1C (28)

- - - -

4028

uint
RWES

[`dEC]
[ dEC]

Analog Input (1 to 12)

Display Precision

Set the precision of the dis-

played value.

[```0]

Whole (105)

[``0;0]

Tenths (94)

[`0;00]

Hundredths (40)

[0;000]

Thousandths (96)

Whole

398
[offset 90]

0x68 (104)

1 to 0xC

(12)

0x14 (20)

- - - -

4020

uint
RWES

[`i;Ca]
[ i.CA]

Analog Input (1 to 12)

Calibration Offset

Offset the input reading to

compensate for lead wire

resistance or other factors

that cause the input read-

ing to vary from the actual

process value.

-1,999.000 to 9,999.000°F or

units

-1,110.555 to 5,555.000°C

0.0

432
[offset 90]

0x68 (104)

1 to 0x10

(16)

0x0C (12

- - - -

4012

float
RWES

[``Ain]
[ Ain]

Analog Input (1 to 12)

Process Value

View the process value.

-1,999.000 to 9,999.000°F or

units

-1,128.000 to 5,537.000°C

- - - -

410
[offset 90]

0x68 (104)

1 to 0xC

(12)

1

0

4001

float
RWES

[`i;Er]
[ i.Er]

Analog Input (1 to 12)

Error Status

View the cause of the most

recent error. If the [Attn]

message is [Er;i1] or
[Er;i2]

, this parameter

will display the cause of

the input error.

[nonE]

None (61)

[OPEn]

Open (65)

[Shrt]

Shorted (127)

[`E;M]

Measurement Error

(149)

[E;CAL]

Bad Calibration Data

(139)

[Er;Ab]

Ambient Error (9)

[E;;Rtd]

RTD Error (141)

[FAiL]

Fail (32)

[Nsrc]

Not Sourced (246)

None

412
[offset 90]

0x68 (104)

1 to 0xC

(12)

2

1

4002

float
RWES

Note: Some values will be rounded off to fit in the four-character display .
Full values can be read with other interfaces .

If there is only one instance of a menu, no submenus will appear .

R: Read

W: Write

E:

EEPROM

S:

User

Set