Output 7 and 8 mechanical relays, form a – Watlow EZ-ZONE RM Limit Module Rev C User Manual

Page 27

Advertising
background image

Warning:

ç

Use National Electric (NEC) or other
country-specific standard wiring and
safety practices when wiring and
connecting this controller to a power
source and to electrical sensors or pe-
ripheral devices. Failure to do so may
result in damage to equipment and
property, and/or injury or loss of life.

Note:

Maximum wire size termination and

torque rating:
• 0.0507 to 3.30 mm2 (30 to 12 AWG)
single-wire termination or two 1.31
mm2 (16 AWG)
• 0.8 Nm (7.0 in-lb.) torque

Note:

Adjacent terminals may be labeled
differently, depending on the model
number.

Note:

To prevent damage to the controller,
do not connect wires to unused ter-
minals.

Note:

Maintain electrical isolation between
digital input-outputs, switched dc/open
collector outputs and process outputs

to prevent ground loops.

Watlow EZ-ZONE

®

RML Module

24

Chapter 2 Install and Wire

• 5 A at 240VÅ (ac) or 30VÎ (dc)

maximum resistive load

• 20 mA at 24V minimum load
• 125 VA pilot duty @ 120/240VÅ

(ac), 25 VA at 24VÅ (ac)

• 100,000 cycles at rated load
• Output does not supply power.
• for use with ac or dc
See Quencharc note.
- Slot D Outputs 1 - 6
RMLx-xx(J)x-xxxx

- Slot E Outputs 7 - 10
RMLx-xxx(J)-xxxx

Output 1 - 4 and 7 - 10 Mechanical Relay, Form A

RML Part # Digit 7, 8 is J

normally open

common

L1
K1
L2
K2
L3
K3
L4
K4

Slot D

normally open

common

normally open

common

normally open

common

L_

K_

Mechanical RelayForm A

Internal Circuitry

normally open

common

L7
K7
L8
K8
L9
K9
L10
K10

Slot E

normally open

common

normally open

common

normally open

common

Output 7 and 8 Mechanical Relays, Form A

RML Part # Digit 8 is B

common

normally open

L7
K7
J7
L8
K8

Slot E

normally closed

normally open

common

• 5 A at 240VÅ (ac) or 30VÎ (dc)

maximum resistive load

• 20 mA at 24V minimum load
• 125 VA pilot duty @ 120/240VÅ

(ac), 25 VA at 24VÅ (ac)

• 100,000 cycles at rated load
• Output does not supply power.
• for use with ac or dc
See Quencharc note.

- Slot E Output 8
RMLx-xxx(B)-xxxx

L8

K8

Mechanical Relay Form A

• 5 A at 240VÅ (ac) or 30VÎ (dc)

maximum resistive load

• 20 mA at 24V minimum load
• 125 VA pilot duty at 120/240VÅ

(ac), 25 VA at 24VÅ (ac)

• 100,000 cycles at rated load
• Output does not supply power.
• for use with ac or dc
See Quencharc note.

- Slot E Output 7
RMLx-xxx(B)-xxxx

normally open

common

normally closed

L _

K _

J _

Mechanical Relay Form C