background image

Watlow EZ-ZONE

®

RML Module

56

Chapter 4 Setup Page

RM Limit Module

Setup Page

Display

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Profibus

Index

Parameter

ID

Data

Type

&

Read/

Write

[SFn;B]
[SFn.b]

Timer (1 to 16)

Source Function B

Set the type of function

that will be used to reset

a retentive timer (reset

signal).

[nonE]

None (61)

[ALM]

Alarm Reset (6)

[`CPE]

Compare (230)

[`Ctr]

Counter (231)

[`dio]

Digital I/O (1142)

[Ent;A]

Profile Event Out A

(233)

[Ent;b]

Profile Event Out B

(234)

[Ent;C]

Profile Event Out C

(235)

[Ent;d]

Profile Event Out D

(236)

[Ent;E]

Profile Event Out E

(247)

[Ent;F]

Profile Event Out F

(248)

[Ent;g]

Profile Event Out G

(249)

[Ent;h]

Profile Event Out H

(250)

[`FUn]

Function Key (1001)

[`lgC]

Logic (239)

[SoF;1]

Special Function Out-

put 1 (1532)

[SoF;2]

Special Function Out-

put 2 (1533)

[SoF;3]

Special Function Out-

put 3 (1534)

[SoF;4]

Special Function Out-

put 4 (1535)

[tMr]

Timer (244)

[`uAr]

Variable (245)

None

7192

[offset 50]

0x83 (131)

1 to 16

2

- - - -

31002

uint
RWES

[`Si;B]
[ Si.b]

Timer (1 to 16)

Source Instance B

Set the instance of the

function selected above.

1 to 250

1

7196

[offset 50]

0x83 (131)

1 to 16

4

- - - -

31004

uint
RWES

[`S2;B]
[ SZ.b]

Timer (1 to 16)

Source Zone B

Set the zone of the function

selected above.

0 to 16

0

7200

[offset 50]

0x83 (131)

1 to 16

6

- - - -

31006

uint
RWES

[sas;b]
[SAS.b]

Timer (1 to 16)

Source Active State B

Set what state will be read

as on.

[high]

High (37)

[LoW]

Low (53)

High

7212

[offset 50]

0x83 (131)

1 to 4

0xC (12)

- - - -

31012

uint
RWES

[``ti]
[ ti]

Timer (1 to 16)

Time

Set the time span that will

be measured.

0 to 9,999.000

1.0

7214

[offset 50]

0x83 (131)

1 to 16

0xD (13)

224

31013

float
RWES

[`LEu]
[ LEv]

Timer (1 to 16)

Active Level

Set which output state will

indicate on.

[high]

High (37)

[LoW]

Low (53)

High

7216

[offset 50]

0x83 (131)

1 to 16

0xE (14)

- - - -

31014

uint
RWES

Note: Some values will be rounded off to fit in the four-character display .