Specifications – Watlow Series 988 User Manual

Page 144

Advertising
background image

A.4

WATLOW Series 988 User’s Manual

Appendix

Specifications

Control Mode
•

Dual input, quad output, optional retransmit of set
point or process variable.

•

Programmable direct and reverse acting control out-
puts.

•

One-step auto-tuning.

Operator Interface
•

Local/remote set point capability.

•

Dual, 4-digit LED displays: upper, 0.4” (10mm); lower,
0.3” (8mm).

•

Mode, Auto/Man, Display, Up and Down keys.

Input
•

Contact input for software function select.

•

Type J, K, T, N, C(W5)

2

, D(W3)

2

, E, R, S, B, Pt 2

2

thermocouple, 1° or 0.1° RTD.

•

0-50mVÎ (dc), 0-20mA, 4-20mA, 0-5VÎ (dc), 1-5VÎ
(dc), 0-10VÎ (dc) process.

•

Slidewire, digital event input or heater current options.

•

Sensor break protection de-energizes control output to
protect system or selectable bumpless transfer to
manual operation. Latching or non-latching.

•

°F or °C display or process units, user selectable.

Sensor Ranges
J t/c:

32 to

1500°F

or

0

to

816°C

K t/c:

-328 to

2500°F

or

-200

to 1371°C

T t/c:

-328 to

750°F

or

-200

to

399°C

N t/c:

32 to

2372°F

or

0

to 1300°C

R t/c:

32 to

3200°F

or

0

to 1760°C

S t/c:

32 to

3200°F

or

0

to 1760°C

B t/c:

1598 to

3300°F

or

870

to 1816°C

E t/c:

-328 to

1470°F

or

-200

to

799°C

C t/c (W5)

2

:

32 to

4200°F

or

0

to 2316°C

D t/c (W3)

2

:

32 to

4200°F

or

0

to 2316°C

Pt 2

2

:

32 to

2543°F

or

0

to 1395°C

1°RTD (JIS):

-328 to

1166°F

or

-200

to

630°C

1°RTD (DIN): -328 to

1472°F

or

-200

to

800°C

0.1°RTD
(JIS and DIN):-99.9 to 999.9°F

or -73.3

to 537.7°C

0-5VÎ (dc):

-999 to

9999

1-5VÎ (dc):

-999 to

9999

0-10VÎ (dc):

-999 to

9999

0-20mA:

-999 to

9999

4-20mA:

-999 to

9999

0-50mVÎ (dc): -999 to

9999

Slidewire:

100 to

1200

Ω

Current:

0 to

50A

Potentiometer:

0 to

1200

Ω

Output Options

•

Solid-state relay, 0.5A @ 24VÅ (ac) min., 253VÅ (ac)
max., opto-isolated, burst fire. With or without contact
suppression.

•

Open collector: Max. voltage 42VÎ (dc), max. current
1A.

•

Switched dc signal: Min. turn-on voltage of 3VÎ (dc)
into min. 500

Ω load; max. On voltage not greater than

32VÎ (dc) into an infinite load, isolated.

•

Electromechanical relay

1

, Form C, 5A @ 120/240VÅ

(ac), 6A @ 28VÎ (dc), 1/8 hp. @ 120VÅ (ac) or
125VA @ 120VÅ (ac). With or without contact sup-
pression. Off-state output impedance with RC sup-
pression is 20k

Ω.

•

Process, 0-20mA, 4-20mA into 800

Ω maximum, 0-

5VÎ (dc), 1-5VÎ (dc) or 0-10VÎ (dc) into 1k

Ω mini-

mum

1

, reverse acting, isolated.

•

Electromechanical relay, Form A/B, 5A @ 120/240VÅ
(ac), 6A @ 28VÎ (dc), 1/8 hp. @ 120VÅ (ac) or
125VA @ 120VÅ (ac). Without contact suppression.

•

External transmitter power supply, 5V ±5% @ 30mA,
12V ±5% @ 30mA or 20V ±5% @ 30mA.

•

EIA/TIA-232 communications or EIA/TIA-485, EIA/TIA-
422 communications, opto-isolated.

Accuracy
•

Calibration accuracy and sensor conformity: ± 0.1% of
span, ±1 LSD, 77°F ± 5°F (25°C ± 3°C) ambient and
rated line voltage ±10%.

•

Accuracy span: 1000°F (540°C) minimum.

•

Temperature stability: ± 0.2°F/°F (0.1°C/°C) change in
ambient.

•

Voltage stability: ± 0.01% of span /% of rated line volt-
age.

Agency Approvals
•

and

to UL873, File #43684

•

CE: 89/336/EEC Electromagnetic Compatibility
Directive.
EN 61326 Industrial Immunity, Class A Emissions.

•

73/23/EEC Low-Voltage Directive.
EN 61010-1: 1993 Safety.

•

IP65 / NEMA 4X

Terminals
•

#6 compression universal head screws (tighten to 5
inch/pounds maximum), accepts 20-14 gauge wire.

Line Voltage/Power
•

100 to 240VÅ

1

(ac) +10%/-15%, 50/60Hz, ± 5%.

•

24 to 28V‡

1

(ac/dc) +10%/-15%, 50/60Hz, ±5%.

•

16VA maximum.

•

Fused internally (factory replaceable only) Slo-Blo®
type (time-lag): 2A, 250V for high-voltage versions;
5A, 250V for low-voltage versions.

•

Non-volatile memory retains data if power fails.

Operating Environment
•

32 to 149°F (0 to 65°C), 0 to 90% RH, non-condens-
ing.

Storage Temperature
•

-40 to 185°F (-40 to 85°C).

Mechanical
• 1/8 DIN panel mount, NEMA 4X (IP65 equivalent) front

panel.

• Overall width x height x depth:

horizontal - 4.03" x 2.18" x 4.74"
(102mm x 55mm x 120mm);
vertical - 2.18" x 4.03" x 4.74"
(55mm x 102mm x 120mm).

• Depth behind panel; 4.06" (103mm).
• Weight: less than or equal to 14.0oz (0.40kg).
Sample/Update Rates
•

1 input: 10Hz.

•

2 inputs: 5Hz.

•

Retransmit: 1Hz.

•

Remote set point: 1Hz.

•

PID: 10Hz.

•

Outputs: 10Hz.

•

Display: 2Hz.

•

Alarm Outputs: 1 Hz

Resolution
•

Inputs: 16 bits.

•

Outputs: 12 bits.

1

Electromechanical relays are warranted for 100,000 clo-

sures only. Solid-state switching devices are recom-
mended for applications requiring fast cycle times or
extended service life.

2

Not an ANSI symbol.

(2221)