Csac, Setup-global, Cascade action – Watlow Series 988 User Manual
Page 65

WATLOW Series 988 User’s Manual
4.37
Setup Menus, Chapter 4
Setup-Global
Cascade Action
Select the control action between the inner and outer loop of a cas-
cade system.
• Direct action
[`dir] makes the percent output from the outer loop
directly proportional to the set point of the inner loop (input 2). A 100%
signal in the outer loop will set the inner loop to range high 2
[`rH2]
(Input Menu). A 0% signal in the outer loop will set the inner loop to
range low 2
[`rL2] (Input Menu).
• Reverse action
[`rEU] makes the percent output from the outer loop
inversely proportional to the set point of the inner loop (input 2). A 100%
signal in the outer loop will set the inner loop to range low 2
[`rL2]
(Input Menu). A 0% signal in the outer loop will set the inner loop to
range high 2
[`rH2] (Input Menu).
[CSAC] This prompt appears only on controllers equipped with enhanced
software (98_B-_ _ _ _-_ _ _ _) and with
[CntL] set to [CSCd].
Default
↓
[`dir]
[`rEU]
[CASC]
[CASC]
[CSAC]