Re2a] [re2b] [it2a] [it2b, Operation-pid a or b, Reset, output 2 – Watlow Series 988 User Manual
Page 90: Integral, output 2

5.14
WATLOW Series 988 User’s Manual
Operation Menus, Chapter 5
Operation-PID A or B
Reset, Output 2
Tune reset to eliminate the offset or droop between the set point and
the actual process temperature for PID A output 2. When set to
[```0]
reset is disabled.
[rE2A] This prompt appears only if [`dFL] (Calibration Menu) is set to
[``US] and [Pb2A] is set higher than [```0].
If
Default
↓
↓
[00)0] … [99(9]
repeats/min.
[rE2A]
[rE2A]
[`Pdr]
[=0)0] %… [``)0] %… [10)0] %
[ALG0]
[rE2A]
[rE2A]
[rE2A]
(Global Menu)
Integral, Output 2
Tune integral to eliminate the offset or droop between the set point
and the actual process temperature for PID output 2. When set to
[```0] integral is disabled.
[It2A] This prompt appears only if [`dFL] (Calibration Menu) is set to
[``SI] and [Pb2A] is set higher than [```0].
Default
↓
[`)00] … [9(99]
repeats / min.
[It2A]
[It2A]
[rE2A]
[rE2b]
[It2A]
[It2b]
˜
NOTE:
The PID B Menu
appears only on
controllers with
enhanced software
(98_B-_ _ _ _-_ _ _ _).