Proc] [stpt, Setup-global, Crossover process value – Watlow Series 988 User Manual
Page 67: Crossover set point value

WATLOW Series 988 User’s Manual
4.39
Setup Menus, Chapter 4
Setup-Global
Crossover Process Value
Select the process value at which the control algorithm will crossover
between PID A and PID B. PID A is active below this value and PID B is
active above this value.
• This value cannot be set lower than range low 1
[`rL1] or higher than
range high 1
[`rH1].
[Proc] This prompt appears only on controllers with [Pid2] set to [Proc].
Default
↓
[`rL1]
[`rH1]
[Proc]
[Proc]
Crossover Set Point Value
Select the set point value at which the control algorithm will
crossover between PID A and PID B. PID A is active below this value and
PID B is active above this value.
• This value cannot be set lower than range low 1
[`rL1] or higher than
range high 1
[`rH1].
[StPt] This prompt appears only on controllers with [Pid2] set to [StPt].
Default
↓
[`rL1]
[`rH1]
[StPt]
[StPt]
[Proc]
[StPt]