background image

WATLOW Series 988 User’s Manual

2.13

Installation and Wiring, Chapter 2

Output 2 Wiring

Figure 13b —

Switched DC, Open Collector

98 _ _ - _ _ _ C - _ _ _ _

Maximum voltage: 42VО

О (dc)

Maximum current: 1A

15

External

Load

+

16

17

-

COM

Figure 13d —

0-5V

О

О, 1-5VО

О and 0-10VО

О (dc) Process

98 _ _ - _ _ _ F - _ _ _ _

Minimum load impedance: 1K

Ω

Figure 13c —

0-20mA and 4-20mA Process

98 _ _ - _ _ _ F - _ _ _ _

Maximum load impedance: 800

Ω

15

+

-

17

16

+

-

17

Figure 13e —

External Signal Conditioner Power Supply

98 _ _ - _ _ _ T - _ _ _ _

15

16

1

2

+

-

+V

-V

Transmitter

4-20mA out

Input
1 or 2

-

+

Figure 13a —

AC Outputs

Solid-state Relay with Contact Suppression

98 _ _ - _ _ _ B - _ _ _ _

0.5 amps, minimum off-state impedance: 20K

Ω

Electromechanical Relay with Contact Suppression
(Suppression between NO and COM contacts only)

98 _ _ - _ _ _ D - _ _ _ _

Form C, 5 amps, minimum off-state impedance: 20K

Ω

Electromechanical Relay without Contact Suppression

98 _ _ - _ _ _ E - _ _ _ _

Form C, 5 amps off-state impedance: 31M

Ω

Solid-state Relay without Contact Suppression

98 _ _ - _ _ _ K - _ _ _ _

0.5 amps, off-state impedance: 31M

Ω

External

Load

COM

L1

L2

Fuse

NO

15

16

NC

17

(#17 for D & E outputs only)

+

Internal Circuitry

15

16

17

790

Ω

19 to 32VÎ (dc)

NOTE:
Successful installa-
tion requires five
steps:
• Model number and
software choice
(Appendix);
• DIP switch set-
tings (Chapter 1);
• Sensor match
(Chapter 2 and
Appendix);
• Sensor installation
(Chapter 2); and
• Wiring (Chapter 2).

˜

NOTE:
Input-to-output iso-
lation is defeated
when the external
signal conditioner
power supply is
used to power a
transmitter connect-
ed to input 1 or
input 2.

NOTE:
Switching inductive
loads (relay coils,
solenoids, etc.) with
the mechanical
relay or solid state
relay output options
requires using an
R.C. suppressor.
Watlow carries the
R.C. suppressor
Quencharc brand
name, which is a
trademark of ITW
Paktron. Watlow
Part No. 0804-0147-
0000.

Loop powered

Advertising