4 swapping the high/low-pressure side connection, 1 rotating pressure-detector section 180, 2 using the communicator – Yokogawa EJA110E User Manual

Page 25: Rotating pressure-detector section 180° -3, Using the communicator -3, Important

Advertising
background image

<4. Installation>

4-3

IM 01C25B01-01E

4.4 Swapping the High/Low-

pressure Side Connection

IMPORTANT

This section is applicable only for EJ110,

EJ120, and EJ130 differential

transmitters, and not applicable for gauge or

absolute pressure transmitters.

4.4.1 Rotating Pressure-detector Section

180°

This procedure can be applied only to a transmitter

with a vertical impulse piping type.
The procedure below can be used to turn the

pressure detector assembly 180°. Perform

this operation in a maintenance shop with the

necessary tools laid out and ready for use, and then

install the transmitter in the field after making the

change.

1) Use an Allen wrench (JIS B4648, nominal 2.5

mm) to remove the two setscrews at the joint

between the pressure-detector section and

transmitter section.

2) Leaving the transmitter section in position,

rotate the pressure-detector section 180°.

3) Tighten the two setscrews to fix the pressure-

detector section and transmitter section

together (at a torque of 1.5 N·m).

Reposition the process connector and drain

(vent) plugs to the opposite side as described in

subsection 4.3.

F0405.ai

Process connector

Setscrew

Before

After rotating 180°

Figure 4.5

Before and After Modification

4.4.2 Using the Communicator

This method is applicable only to the Model

EJ110, EJ120, and EJ130.
With a communicator, you can change which

process connection is used as the high-pressure

side without mechanically rotating the pressure-

detector section 180 as described in subsection

4.4.1. To change, call parameter ‘D15: H/L SWAP’

for BRAIN Communication or ‘H/L swap’ for HART

Communication and select REVERSE (right side:

low pressure; left side: high pressure) or select

NORMAL to change back to normal (right side: high

pressure; left side: low pressure).

Output

Input

NORMAL

REVERSE

F0406.ai

Figure 4.6

Input/Output Relationship

IMPORTANT

Since the H/L label plate on the capsule

assembly will remain unchanged, use this

function only when you cannot switch the

impulse piping. If the ‘H/L SWAP’ parameter

setting is changed, the input/output relationship

is reversed as shown in figure 4.6; be sure this is

understood by all.