2 troubleshooting flowcharts, Troubleshooting flowcharts -7 – Yokogawa EJA110E User Manual

Page 46

Advertising
background image

<8. Maintenance>

8-7

IM 01C25B01-01E

8.5.2 Troubleshooting Flowcharts

Connect communicator and check self-diagnostics.

Does the self-diagnostic

indicate problem location?

Contact Yokogawa service personnel.

F0807.ai

The following sorts of symptoms indicate that transmitter

may not be operating properly.

Example : • There is no output signal.

• Output signal does not change even though

process variable is known to be varying.

• Output value is inconsistent with value

inferred for process variable.

Is power supply

polarity correct?

Are power

supply voltage and load

resistance correct?

Refer to Section 6.3 to check/correct

polarity at each terminal from power

supply to the terminal box.

Fix pressure leaks, paying particular

attention to connections for impulse

piping,pressure-detector section, etc.

Fully close equalizing valve, and fully

open high pressure and low pressure

valves.

Refer to Section 6.6 for rated voltage

and load resistance.

Find/correct broken conductor or

wiring error.

Are valves opened or

closed correctly?

Is there any pressure leak?

Is there

continuity through the

transmitter loop wiring?

Do the loop numbers

match?

YES

NO

YES

NO

NO

YES

NO

NO

YES

YES

NO

YES

Refer to error message summary in

Subsection 8.5.3 or in each

communication manual to take actions.

Connect a communicator and check self-diagnostics.

Does the self-

diagnostic indicate problem

location?

Contact Yokogawa service personnel.

F0808.ai

Is power supply

polarity correct?

Are valves opened or

closed correctly?

Refer to error message summary in

each communication manual to take

actions.

YES

NO

NO

YES

Refer to Section 6.3 to check/correct

polarity at each terminal from power

supply to the terminal box.

Refer to individual model user manuals

and connect piping as appropriate for

the measurement purpose.

Fix pressure leaks, paying particular

attention to connections for impulse

piping, pressure-detector section, etc.

Fully close equalizing valve, and fully

open high pressure and low pressure

valves.

NO

YES

YES

NO

YES

Adjust the zero point.

NO

NO

YES

Is there any pressure leak?

Is impulse piping

to high pressure and low

pressure side correct?

Is zero point

adjusted correctly?

Output travels beyond 0% or 100%.