<6. Wiring>

6-2

IM 01C25B01-01E

6.3.4 Check Meter Connection

Available only when /AL is not specified.
Connect the check meter to the CHECK + and

– terminals. (Use hooks.)

• A 4 to 20 mA DC output signal from the CHECK

+ and – terminals.

(Note) Use a check meter whose internal resistance is 10 Ω or

less.

SUPPL

Y

PULSE

CHECK

ALARM

Transmitter terminal box

F0604.ai

Power supply

+

Check meter

Figure 6.4

Check Meter Connection

6.3.5 Status Output Connection

When option code /AL is specified, connect the

external wiring as shown in Figure 6.5.
To configure and activate the process alarm

function and status output, it is necessary to set

some parameters. Refer to each communication

manual for procedures.

SUPPL

Y

PULSE

CHECK

ALARM

Transmitter

terminal box

Magnetic

valve

AC power supply

External power

supply 30V DC,

120mA max

+

250Ω

24V DC

Use two-wire separately shielded cables.

Distributor

Shielded cable

F0605.ai

Figure 6.5

Status Output Connection

6.4 Wiring

6.4.1 Loop Configuration

Since the DPharp uses a two-wire transmission

system, signal wiring is also used as power wiring.
DC power is required for the transmitter loop. The

transmitter and distributor are connected as shown

below.
For details of the power supply voltage and load

resistance, see section 6.6; for communications line

requirements, see section 9.1.

(1) General-use Type and Flameproof Type

Hazardous Location

Nonhazardous Location

Transmitter terminal box

Distributor

(Power supply unit)

Receiver

instrument

F0606.ai

SUPPL

Y

PULSE

CHECK

ALARM

Figure 6.6

Connection between Transmitter and

Distributor

(2) Intrinsically Safe Type
With the intrinsically safe type, a safety barrier must

be included in the loop.

Hazardous Location

Nonhazardous Location

Transmitter terminal box

Distributor

(Power supply unit)

Receiver

instrument

Safety barrier

F0607.ai

SUPPL

Y

PULSE

CHECK

ALARM

Figure 6.7

Connection between Transmitter and

Distributor

6.4.2 Wiring Installation

(1) General-use Type and Intrinsically Safe

Type

With the cable wiring, use a metallic conduit or

waterproof glands.

• Apply a non-hardening sealant to the terminal

box connection port and to the threads on the

flexible metal conduit for waterproofing.

F0608.ai

Flexible metal conduit

Wiring metal

conduit

Tee

Drain plug

Apply a non-hardening

sealant to the threads for

waterproofing.

Figure 6.8

Typical Wiring Using Flexible Metal

Conduit