<8. Maintenance>

8-8

IM 01C25B01-01E

Connect a communicator and check self-diagnostics.

Contact Yokogawa service personnel.

F0809.ai

Are valves opened or

closed correctly?

Is impulse piping

connected correctly?

Refer to error message summary in

each communication manual to take

actions.

Refer to Section 6.6 for rated voltage

and load resistance.

Provide lagging and/or cooling, or allow

adequate ventilation.

Refer to Section 8.2 when selecting

instruments for calibration.

Fully close equalizing valve, and fully

open high pressure and low pressure

valves.

Refer to individual model user manuals

and connect piping as appropriate for

the measurement purpose.

Adjust the output.

Is transmitter

installed where there is

marked variation in

temperature?

Is output adjusted correctly?

Large output error.

Does the self-

diagnostic indicate problem

location?

Are power supply

voltage and load resistance

correct?

Were appropriate

instruments used for

calibration?

YES

NO

YES

NO

NO

YES

NO

YES

NO

YES

NO

YES

NO

YES