<4. Installation>

4-4

IM 01C25B01-01E

4.5 Rotating Transmitter Section

The transmitter section can be rotated

approximately 360° (180° to either direction or

360° to one direction from the original position at

shipment, depending on the configuration of the

instrument.) It can be fixed at any angle within

above range.

1) Remove the two setscrews that fasten the

transmitter section and capsule assembly,

using the Allen wrench.

2) Rotate the transmitter section slowly and stop it

at designated position.

3) Tighten the two setscrews to a torque of 1.5

N·m.

IMPORTANT

Do not rotate the transmitter section more than

the above limit.

F0407.ai

Vertical impulse piping type

Horizontal impulse piping type

Pressure-detector section

Transmitter section

Rotate 0 to ±180° segments

Rotate 0 to ±180° segments

Transmitter section

Pressure-detector section

Conduit connection

Conduit connection

Zero-adjustment screw

Stopper

Figure 4.7

Rotating Transmitter Section (Left Side

High Pressure Type)

4.6 Changing the Direction of

Integral Indicator

IMPORTANT

Always turn OFF power, release pressure and

remove a transmitter to non-hazardous area

before disassembling and reassmbling an

indicator.

An integral indicator can be installed in the

following three directions. Follow the instructions in

section 8.4 for removing and attaching the integral

indicator.

F0408.ai

Figure 4.8

Integral Indicator Direction