2 troubleshooting flowcharts, Troubleshooting flowcharts -5 – Yokogawa EJX118A User Manual

Page 40

Advertising
background image

<8. Maintenance>

7-5

IM 01C25H01-01E

This transmitter is equipped with a self-diagnostic

function which will be useful in troubleshooting,

and the transmitter equipped with an integral

indicator will show an alarm code as a result of self-

diagnosis.

See subsection 7.5.3 for the list of alarms.

See also each communication manual.

Abnormalities appear in measurement.

: Areas where self-diagnostic offers support

Is process variable

itself abnormal?

Inspect the

process system.

Isolate problem in

measurement system.

Does problem exist in

receiving instrument?

Check/correct

environmental conditions.

Inspect receiver.

Check transmitter.

Check/correct operating

conditions.

Measurement system problem

F0704.ai

YES

NO

NO

YES

Environmental conditions

Operating conditions

Transmitter itself

Figure 7.5 Basic Flow and Self-Diagnostics

7.5.2 Troubleshooting Flowcharts

Connect communicator and check self-diagnostics.

Does the self-diagnostic

indicate problem location?

Contact Yokogawa service personnel.

F0705.ai

The following sorts of symptoms indicate that the

transmitter may not be operating properly.

Example : • There is no output signal.

• Output signal does not change even though

process variable is known to be varying.

• Output value is inconsistent with value

inferred for process variable.

Is power supply

polarity correct?

Are power

supply voltage and load

resistance correct?

Refer to Section 5.3 to check/correct

polarity at each terminal from power

supply to the terminal box.

Refer to Section 5.6 for rated voltage

and load resistance.

Find/correct broken conductor or

wiring error.

Is there

continuity through the

transmitter loop wiring?

Do the loop numbers

match?

YES

NO

NO

YES

NO

YES

NO

YES

Refer to error message summary in

Subsection 7.5.3 or in each

communication manual to take actions.