<8. Maintenance>

7-6

IM 01C25H01-01E

Connect BRAIN TERMINAL and check self-diagnostics.

Does the self-

diagnostic indicate problem

location?

Contact Yokogawa service personnel.

F0706.EPS

Is power supply

polarity correct?

Are high

and low pressure side

diaphragm seals correctly

connected to the

process?

Refer to error message summary in each

communication manual to take actions.

YES

NO

NO

YES

Check/correct polarity at each terminal

from power supply to the terminal box.

Use the transmitter within the

measurement range shown on the

data plate.

Correct the connections.

NO

YES

YES

Adjust the zero point.

NO

NO

YES

Is the liquid level as specified?

Is zero point

adjusted correctly?

Output travels beyond 0% or 100%.

Connect BRAIN TERMINAL and check self-diagnostics.

Contact Yokogawa service personnel.

F0707.ai

Are power

supply voltage and load

resistance correct?

Is external noise

contained in the output?

Refer to error message summary in each

communication manual to take actions.

Bind capillaries together as far as

possible or provide lagging.

Provide lagging and/or heat insulation,

or allow adequate ventilation.

Refer to Section 7.2 when selecting

instruments for calibration.

Refer to Section 5.6 to obtain the rated

voltage and load resistance.

Avoid noise by providing complete

grounding, or using shielded wires.

Adjust the output.

Does

the ambient

temperature significantly

differ between the high and low

pressure side

capillaries?

Is output adjusted correctly?

Large output error.

Does the self-

diagnostic indicate the problem

location?

Is transmitter

installed where there is

marked variation in

temperature?

Are excess

capillaries secured?

YES

NO

YES

NO

NO

YES

NO

YES

NO

YES

NO

YES

NO

YES

Secure them so that they are not

moved by wind or vibration.

Were appropriate

instruments used for

calibration?

YES

NO