IM 01C21D01-01E

2-7

2. HANDLING CAUTIONS

• Electrical Connection:
The type of electrical connection is stamped near

the electrical connection port according to the
following marking.

T0202.EPS

F0210.EPS

Location of the marking

Note 4. Operation

• WARNING:
WHEN AMBIENT TEMPERATURE

≥ 55°C,

USE THE HEAT-RESISTING CABLES

≥ 90°C.

Note 5. Special Conditions for Safe Use

• WARNING:
IN THE CASE WHERE THE ENCLOSURE OF

THE PRESSURE TRANSMITTER IS MADE OF
ALUMINUM, IF IT IS MOUNTED IN AN AREA
WHERE THE USE OF ZONE 0 IS REQUIRED,
IT MUST BE INSTALLED SUCH, THAT, EVEN
IN THE EVENT OF RARE INCIDENTS, IGNI-
TION SOURCES DUE TO IMPACT AND
FRICTION SPARKS ARE EXCLUDED.

F0211.EPS

EJA Series Pressure
Transmitters

IECEx certified
Safety Barrier

Supply

Hazardous Location

Nonhazardous Location

General
Purpose
Equipment

+

+

+

+

[Intrinsically Safe]

Group I/IIC, Zone 0

F0212.EPS

EJA Series Pressure
Transmitters

Supply

Hazardous Location

Nonhazardous Location

+

+

Not Use
Safety Barrier

[type n]

IECEx Certified
Equipment [nL]

Group IIC, Zone 2

b. IECEx Flameproof Type

Caution for IECEx flameproof type.

Note 1. Model EJA Series differential, gauge, and

absolute pressure transmitters with
optional code /SU2 are applicable for use
in hazardous locations:

• No. IECEx KEM 06.0005
• Applicable Standard: IEC60079-0:2004,
IEC60079-1:2003
• Type of Protection and Marking Code:
Ex d IIC T6...T4
• Enclosure: IP67
• Maximum Process Temperature: 120

°C (T4),

100

°C (T5), 85°C (T6)

• Ambient Temperature: –40 to 75

°C (T4), –40 to

80

°C (T5), –40 to 75°C (T6)

• Supply Voltage: 42 V dc max.
• Output Signal: 4 to 20 mA dc

Note 2. Wiring

• In hazardous locations, the cable entry devices shall

be of a certified flameproof type, suitable for the
conditions of use and correctly installed.

• Unused apertures shall be closed with suitable

flameproof certified blanking elements. (The plug
attached is certificated as the flame proof IP67 as a
part of this apparatus.)

• In case of ANSI 1/2 NPT plug, ANSI hexagonal

wrench should be applied to screw in.

Note 3. Operation

• WARNING:
AFTER DE-ENERGIZING, DELAY 10 MINUTES

BEFORE OPENING.

• WARNING:
WHEN AMBIENT TEMPERATURE

≥ 70°C,

USE THE HEAT-RESISTING CABLES

≥ 90°C.

• Take care not to generate mechanical sparking

when accessing to the instrument and peripheral
devices in a hazardous location.

Note 4. Maintenance and Repair

• The instrument modification or parts replacement

by other than authorized representative of
Yokogawa Electric Corporation is prohibited and
will void IECEx Certification.

2.9.4 CENELEC ATEX (KEMA)

Certification

(1) Technical Data

a. CENELEC ATEX (KEMA) Intrinsically Safe

Type

Caution for CENELEC ATEX (KEMA) Intrinsi-
cally safe type.