Indication and input pressure indication, User-set engineering unit display – Yokogawa EJA310A User Manual

Page 43

Advertising
background image

IM 01C21D01-01E

8-10

8. BRAIN TERMINAL BT200 OPERATION

% indication and
input pressure
indication

Transmitter is set

for “% display” when

shipped.

D20: DISP SELECT
NORMAL %
INP PRES
PRES & %

User-set engineering
unit display

D20: DISP SELECT
USER SET
USER & %

D21: DISP UNIT

D22: DISP LRV

D23: DISP HRV

Set for user-set
engineering unit display.

Set a unit to be
displayed on the BT200.

Set a numeric value for
engineering unit for 4 mA
output (LRV).

Set a numeric value for
engineering unit for 20 mA
output (HRV).

F0818.EPS

a. Display Selection (D20: DISP SELECT)

Follow the instructions given to the below to change
the range of integral indication scales.

When USER SET is selected, the user set values of
integral indication and A11: ENGR. OUTPUT
parameter are indicated.

• Example: Set the integral indicator scale to

engineering units display.

The “%” disappears from the

integral indicator display.

ESC

SET
D20:DISP SELECT
USER SET

FEED

NO

OK

SET
D20:DISP SELECT
NORMAL %
<NORMAL %>
<USER SET>
<USER & %>
<INP PRES>

Use the or key

to select “USER SET.”

Press the key twice to

enter the setting.

Press the (OK) key.

F0819.EPS

b. Setting User-set Engineering Unit

(D21: DISP UNIT)

This parameter allows entry of the engineering units
to be displayed on the BT200. When the instrument
is shipped, this is set as specified in the order.

Follow the procedure below to change this setting.

This parameter need not be set for % display.

• Example: Set an engineering unit M.

CODE

CAPS

CLR

ESC

SET
D21:DISP UNIT
M

FEED

NO

OK

SET
D21:DISP UNIT

M_

Set “M.”

Press the key twice to

enter the setting.

Press the (OK) key.

F0820.EPS

c. Lower and Higher Range Value Setup

in Engineering Unit (D22: DISP LRV,
D23: DISP HRV)

These parameter items are used to set the lower and
higher range values for the engineering unit display.

When the instrument is shipped, these are set as
specified in the order. Follow the procedure below to
change these settings. Note that these parameters
need not be set for % display.

• Example: Set lower range value (LRV) to –50

and higher range value (HRV) to 50.

FEED

NO

OK

SET
D23:DISP HRV
50M

Press the (OK) key.

F0821.EPS

DEL

CLR

ESC

DATA

DIAG

PRNT

ESC

PARAM
D21:DISP UNT
M
D22:DISP LRV
– 50M
D23:DISP HRV
50M

DEL

CLR

ESC

SET
D22:DISP LRV
0M
- 50

Set “–50.”

Press the key twice to

enter the setting.

Setting LRV

Setting HRV

Set “50.”

Press the key twice to

enter the setting.

SET
D23:DISP HRV
100M
+ 50