2 impulse piping connection examples, Impulse piping connection examples -2 – Yokogawa EJA310A User Manual

Page 25

Advertising
background image

IM 01C21D01-01E

5-2

5. INSTALLING IMPULSE PIPING

(3) Impulse Piping Slope

The impulse piping must be routed with only an
upward or downward slope. Even for horizontal
routing, the impulse piping should have a slope of at
least 1/10 to prevent condensate (or gases) from
accumulating in the pipes.

(4) Preventing Freezing

If there is any risk that the process fluid in the impulse
piping or transmitter could freeze, use a steam jacket or
heater to maintain the temperature of the fluid.

NOTE

After completing the connections, close the valves
on the process pressure taps (

main valves), the

valves at the transmitter (

stop valves), and the

impulse piping drain valves, so that condensate,
sediment, dust and other extraneous material
cannot enter the impulse piping.

5.2 Impulse Piping Connection

Examples

Figure 5.2 shows examples of typical impulse piping
connections. Before connecting the transmitter to the
process, study the transmitter installation location, the
process piping layout, and the characteristics of the
process fluid (corrosiveness, toxicity, flammability,
etc.), in order to make appropriate changes and
additions to the connection configurations.

Note the following points when referring to these
piping examples.

• The transmitter impulse piping connection is shown

for a vertical impulse piping connection configura-
tion in which the direction of connection is either
upwards or downwards.

• If the impulse piping is long, bracing or supports

should be provided to prevent vibration.

• The impulse piping material used must be compat-

ible with the process pressure, temperature, and
other conditions.

• A variety of process pressure tap valves (main

valves) are available according to the type of
connection (flanged, screwed, welded), construction
(globe, gate, or ball valve), temperature and
pressure. Select the type of valve most appropriate
for the application.

F0503.EPS

Liquid Gas Steam

Union or flange

Tee

Tee

Drain plug

Drain valve

Drain valve

Drain plug

Union or flange

Union or

flange

Union or flange

Tap valve

Tap valve

Tee

Drain valve

Drain plug

Tap valve

Figure 5.2 Impulse Piping Connection Examples