Yokogawa EJA310A User Manual

Page 16

Advertising
background image

IM 01C21D01-01E

2-8

2. HANDLING CAUTIONS

Note 1. Model EJA Series differential, gauge, and

absolute pressure transmitters with
optional code /KS2 for potentially explo-
sive atmospheres:

• No. KEMA 02ATEX1030 X
• Applicable Standard: EN50014:1997,

EN50020:1994, EN50284:1999

• Type of Protection and Marking code:

EEx ia IIC T4

• Temperature Class: T4
• Enclosure: IP67
• Process Temperature: 120

°C max.

• Ambient Temperature: –40 to 60

°C

Note 2. Electrical Data

• In type of explosion protection intrinsic safety EEx

ia IIC only for connection to a certified intrinsically
safe circuit with following maximum values:

Ui = 30 V
Ii = 165 mA
Pi = 0.9 W
Effective internal capacitance; Ci = 22.5 nF
Effective internal inductance; Li = 730

µH

Note 3. Installation

• All wiring shall comply with local installation

requirements. (Refer to the installation diagram)

Note 4. Maintenance and Repair

• The instrument modification or parts replacement

by other than authorized representative of
Yokogawa Electric Corporation is prohibited and
will void KEMA Intrinsically safe Certification.

Note 5. Special Conditions for Safe Use

• In the case where the enclosure of the Pressure

Transmitter is made of aluminium, if it is mounted
in an area where the use of category 1 G apparatus
is required, it must be installed such, that, even in
the event of rare incidents, ignition sources due to
impact and friction sparks are excluded.

Transmitter

Supply

Safety Barrier *1

Nonhazardous Location

[Installation Diagram]

Hazardous Location

+

+

F0208.EPS

*1: In any safety barriers used the output current must be limited

by a resistor “R” such that Imaxout-Uz/R.

b. CENELEC ATEX (KEMA) Flameproof Type

Caution for CENELEC ATEX (KEMA) flameproof
type.

Note 1. Model EJA Series differential, gauge, and

absolute pressure transmitters with
optional code /KF2 for potentially explo-
sive atmospheres:

• No. KEMA 02ATEX2148
• Applicable Standard: EN50014:1997,

EN50018:2000

• Type of Protection and Marking Code: EEx d IIC

T6···T4

• Temperature Class: T6, T5, and T4
• Enclosure: IP67
• Maximum Process Temperature:

85

°C (T6), 100°C (T5), and 120°C (T4)

• Ambient Temperature: T4 and T6; –40 to 75

°C,

T5; –40 to 80

°C

Note 2. Electrical Data

• Supply voltage: 42 V dc max.
• Output signal: 4 to 20 mA

Note 3. Installation

• All wiring shall comply with local installation

requirement.

• The cable entry devices shall be of a certified

flameproof type, suitable for the conditions of use.

Note 4. Operation

• Keep the “CAUTION” label to the transmitter.

CAUTION: AFTER DE-ENERGIZING,
DELAY 10 MINUTES BEFORE OPEN-
ING. WHEN THE AMBIENT
TEMP.

м70°C, USE HEAT-RESISTING

CABLES

м90°C.

• Take care not to generate mechanical sparking

when accessing to the instrument and peripheral
devices in a hazardous location.

Note 5. Maintenance and Repair

• The instrument modification or parts replacement

by other than authorized representative of
Yokogawa Electric Corporation is prohibited and
will void KEMA Flameproof Certification.

c. CENELEC ATEX (KEMA) Intrinsically Safe

Type/CENELEC ATEX (KEMA) Flameproof
Type/ CENELEC ATEX Type n

Model EJA-A Series pressure transmitters with
optional code /KU2 can be selected the type of
protection CENELEC ATEX (KEMA) Intrinsically
Safe, Flameproof or CENELEC ATEX Type n
for use in hazardous locations.

Note 1. For the installation of this transmitter,

once a particular type of protection is selected,
any other type of protection cannot be used.
The installation must be in accordance with the
description about the type of protection in this
user’s manual.