General specifications, 1 standard specifications, General specifications -1 – Yokogawa EJA310A User Manual

Page 60: 1 standard specifications -1

Advertising
background image

IM 01C21D01-01E

10-1

10. GENERAL SPECIFICATIONS

10. GENERAL SPECIFICATIONS

10.1

Standard Specifications

Refer to IM 01C22T02-01E for F

OUNDATION

Fieldbus communication type and IM 01C22T03-
00E for PROFIBUS PA communication type
marked with “

᭛”.

Performance Specifications

See General Specifications sheet, GS 01C21D01-
00E, GS 01C21E01-00E, and GS 01C21E02-00E.

Functional Specifications

Span & Range Limits

EJA310A*:

L

M

Measurement

Span

and Range

Span

Range

Span

Range

psi

(/D1)

2.67 to

40 inH

2

O

0 to

40 inH

2

O

0.38 to

38 inHg

0 to

38 inHg

mbar
(/D3)

6.7 to 100

mmHg

(/D4)

5 to 75

0 to 100

13 to 1300

0 to 1300

0 to 75

9.6 to 960

0 to 960

MPa

0.67 to
10 kPa

0 to

10 kPa

1.3 to

130 kPa

0 to

130 kPa

A

Span

Range

4.3 to 430

0 to 430

0.3 to

30 bar

0 to 30 bar

0.3 to

30 kgf/cm

2

0 to

30 kgf/cm

2

0.03 to 3

0 to 3

T1001.EPS

* The above units are in absolute terms.

EJA430A:

A

Measurement

Span

and Range

Span

Range

psi

(/D1)

4.3 to 430

–15 to 430

bar

(/D3)

0.3 to 30

kgf/cm

2

(/D4)

0.3 to 30

–1 to 30

–1 to 30

MPa

0.03 to 3

–0.1 to 3

T1002.EPS

B

Span

Range

20 to 2000

–15 to 2000

1.4 to 140

1.4 to 140

–1 to 140

–1 to 140

0.14 to 14

–0.1 to 14

EJA440A:

C

Measurement

Span

and Range

Span

Range

psi

(/D1)

720 to 4500

–15 to 4500

bar

(/D3)

50 to 320

kgf/cm

2

(/D4)

50 to 320

–1 to 320

–1 to 320

MPa

5 to 32

–0.1 to 32

T1003.EPS

D

Span

Range

720 to 7200

–15 to 7200

50 to 500

50 to 500

–1 to 500

–1 to 500

5 to 50

–0.1 to 50

Zero Adjustment Limits:

Zero can be fully elevated or suppressed, within
the Lower and Upper Range Limits of the capsule.

External Zero Adjustment “

”:

External zero is continuously adjustable with
0.01% incremental resolution of span. Span may
be adjusted locally using the digital indicator with
range switch.

Output “

”:

Two wire 4 to 20 mA DC output with digital
communications, linear or square root program-
mable. BRAIN or HART FSK protocol are superim-
posed on the 4 to 20 mA signal.

Failure Alarm:

Output status at CPU failure and hardware error;

Up-scale: 110%, 21.6 mA DC or more(standard)
Down-scale: -5%, 3.2 mA DC or less

-2.5%, 3.6 mA DC or less(Optional

code /F1)

Note: Applicable for Output signal code D and E

Damping Time Constant (1st order):

The sum of the amplifier and capsule damping
time constant must be used for the overall time
constant. Amp damping time constant is adjustable
from 0.2 to 64 seconds.

Time Constant (approx. sec)

0.2

L, M, A, B, C, and D

T1004.EPS

Capsule (Silicone Oil)

Ambient Temperature Limits:

* Safety approval codes may affect limits.

–40 to 85°C (–40 to 185°F),
–30 to 80°C (–22 to 176°F) with LCD Display

Process Temperature Limits:

* Safety approval codes may affect limits.

Capsule M, A, B, C and D
–40 to 120°C (–40 to 248°F)
Capsule L for EJA310A
–40 to 100°C (–40 to 212°F)

Maximum Overpressure:

See General Specifications sheet.

Working Pressure Limits (Silicone Oil)

Maximum Pressure Limit:

See ‘Model and Suffix Codes.’

Minimum Pressure Limit:

Capsule

Pressure

L, M, A (EJA310A)

See Figure 1.

A, B (EJA430A)

See GS 01C21E01-00E

C, D (EJA440A)

See GS 01C21E02-00E

Installation

Supply & Load Requirements “

”:

* Safety approvals can affect electrical requirements.

See Section 6.6, ‘Power Supply Voltage and Load
Resistance.’