2. HANDLING CAUTIONS

Note 2. In order to avoid confusion, unnecessary

marking is crossed out on the label other than
the selected type of protection when the
transmitter is installed.

CENELEC ATEX Type of Protection “n”

WARNING

When using a power supply not having a non-
incendive circuit, please pay attention not to
ignite in the surrounding flammable atmosphere.
In such a case, we recommend using wiring
metal conduit in order to prevent the ignition.

• Applicable Standard: EN60079-15
• Referential Standard: IEC60079-0, IEC60079-11
• Type of Protection and Marking Code:

Ex nC IIL T4

• Temperature Class: T4
• Enclosure: IP67
• Process Temperature: 120

°C max.

• Ambient Temperature: –40 to 60

°C

Note 1. Electrical Data

Ui = 30 V
Effective internal capacitance; Ci = 22.5 nF
Effective internal inductance; Li = 730

µH

Note 2. Installation

• All wiring shall comply with local installation

requirements. (refer to the installation diagram)

Note 3. Maintenance and Repair

• The instrument modification or parts replacement

by other than authorized representative of
Yokogawa Electric Corporation is prohibited and
will void Type of Protection “n”.

Power Supply

(Zone 2 only)

Transmitter

Supply

Nonhazardous Location

[Installation Diagram]

Hazardous Location

+

+

F0209.EPS

Ratings of the Power Supply as follows;

Maximum Voltage: 30 V

CENELEC ATEX Type of Protection “Dust”

• Applicable Standard: EN50281-1-1:1997
• Type of Protection and Marking Code: II 1D
• Maximum Surface Temperature:

T65

°C (Tamb.: 40°C), T85°C (Tamb.: 60°C), and

T105

°C (Tamb.: 80°C)

Note 1. Installation instructions

The cable entry devices and blanking elements
shall be of a certificated type providing a level
of ingress protection of at least IP6x, suitable
for the conditions of use and correctly installed.

(2) Electrical Connection

The type of electrical connection is stamped near
the electrical connection port according to the
following marking.

F0200.EPS

Location of the marking

(3) Installation

WARNING

• All wiring shall comply with local installation

requirement and local electrical code.

• There is no need of the conduit seal for both of

Division 1 and Division 2 hazardous locations
because this product is sealed at factory.

• In case of ANSI 1/2 NPT plug, ANSI hexagonal

wrench should be applied to screw in.

(4) Operation

WARNING

• OPEN CIRCUIT BEFORE REMOVING

COVER. INSTALL IN ACCORDANCE WITH
THIS USER’S MANUAL

• Take care not to generate mechanical sparking

when access to the instrument and peripheral
devices in hazardous locations.

(5) Maintenance and Repair

WARNING

The instrument modification or parts replacement
by other than authorized Representative of
Yokogawa Electric Corporation is prohibited and
will void the certification.