Aux -32 – Yokogawa Value Series FX1000 User Manual
Page 45
Advertising

2-32
IM 04L21B01-64EN
Aux
Power
• VT ratio
Specify a value between 1.0 and 6000.0. The decimal place is fixed.
• Point
Set the CT ratio’s decimal place to 0, 1, or 2. This number represents the number of
digits after the decimal point.
• CT ratio
The setting range varies depending on the decimal place.
Setting Range
Decimal Place
10000 to 32000
0
1000.0 to 9999.9
1
0.05 to 999.99
2
• Low-cut power
Specify a value between 0.05 and 20.00. The decimal place is fixed.
Note
Set the VT ratio and CT ratio so that they meet the following condition.
• Secondary rated power × VT ratio × CT ratio < 10 GW.
Phase and Wire System Input Voltage Secondary Rated Power (W)
1P2W
120
100
240
200
1P3W
240
200
3P3W
120
200
240
400
2.5 Entering General Settings