2-32

IM 04L21B01-64EN

Aux

Power

• VT ratio

Specify a value between 1.0 and 6000.0. The decimal place is fixed.

• Point

Set the CT ratio’s decimal place to 0, 1, or 2. This number represents the number of

digits after the decimal point.

• CT ratio

The setting range varies depending on the decimal place.

Setting Range

Decimal Place

10000 to 32000

0

1000.0 to 9999.9

1

0.05 to 999.99

2

• Low-cut power

Specify a value between 0.05 and 20.00. The decimal place is fixed.

Note

Set the VT ratio and CT ratio so that they meet the following condition.
• Secondary rated power × VT ratio × CT ratio < 10 GW.

Phase and Wire System Input Voltage Secondary Rated Power (W)
1P2W

120

100

240

200

1P3W

240

200

3P3W

120

200

240

400