Configuring the FX1000

1

2

3

8

Index

Serial

Serial

For RS-232

• Baud Rate

Select 1200, 2400, 4800, 9600, 19200, or 38400 (bps).

• Parity

Set the parity check method to Odd, Even, or None.

• Data length

Select 7 or 8 (bits). To output the data in binary format, select 8.

• Handshaking

Select Off:Off, XON:XON, XON:RS, or CS:RS.

• Address

For Modbus protocol, enter a value in the range of 1 to 99. For a general purpose

communication protocol, this value is not set.

• Protocol

Settings

Description

Normal

General purpose communication protocol

Modbus

Modbus slave

Master

Modbus master*

* If you select Modbus master, you need to configure the Modbus master settings. See the

next page.

For RS-422/485

• Baud rate

Select 1200, 2400, 4800, 9600, 19200, or 38400 (bps).

• Data length

Select 7 or 8 (bits). To output the data in binary format, select 8.

• Parity

Set the parity check method to Odd, Even, or None.

• Handshaking

Not specified.

• Address

Select a number from 1 to 99.

• Protocol

This is the same as with the RS-232.

2.6 Entering Basic Settings