Measure Function

Burnout

Thermocouple input

Settings

Description

OFF

Sensor disconnections are not detected.

UP

When the sensor burns out, the measured result is set to +over range. The

measured value displays “Burnout.”
For 1-5V input, the FX assumes that the sensor has burned out when the

measured value exceeds the scale upper limit by 10% of the scale width.

(Example: When the measured value is greater than 110 when the scale is from 0

to 100)

DOWN

When the sensor burns out, the measured result is set to –over range. The

measured value displays “Burnout.”
For 1-5V input, the FX assumes that the sensor has burned out when the

measured value falls below the scale lower limit by 5% of the scale width.

(Example: When the measured value is less than –5 when the scale is from 0 to

100)

RJC

• Mode

Sets the reference junction compensation method of the thermocouple input. Select

[Internal] or [External].

Settings

Description

Internal

Uses the reference junction compensation function of the FX.

External

Uses an external reference junction compensation function. When set to

[External], [Volt] is displayed.

• RJC voltage (µV)

The compensation voltage to be added to the input. Set the value in the range of

–20000 µV to 20000 µV.