Configuring the FX1000

1

2

3

8

Index

MODBUS Client

Changes the upper/lower display area

Basic Setting

• Communication interval

Set the read cycle to 1s, 2s, 5s, or 10s.

• Auto recovery

Set the interval for retrying the connection when it is interrupted for some reason.

Select OFF, 10s, 20s, 30s, 1min, 2min, 5min, 10min, 20min, 30min, or 1h.

Modbus Server setting

• Server No.

Select from 1 to 16 for the server registration numbers to be configured.

• Host Name

Set the destination Modbus server name using up to 64 alphanumeric characters.

• If the DNS is used, you can set the host name as a server name.
• You can also set the IP address. In this case, the DNS is not required.

• Port No.

Enter the port number in the range of 0 to 65535 for the selected server. The default

value is 502.

• Unit

Select [Auto] if the unit number of the destination server is not required; Otherwise,

select [Fixed]. If you select [Fixed], the [Unit No.] item is displayed.

• Unit No.

Enter a fixed unit number in the range of 0 to 255.

Command setting

• Command

Set the command type.

Settings

Description

R-Math

Read to the communication input data (32-bit floating point type) from the

server.

Write

Write the measurement channel (16-bit signed integer type) to the server.

W-Math

Write the computation channel (32-bit signed integer type) to the server.

You can only select [R-Math] or [W-Math] on models that have the /M1, /PM1, or /PWR1

option.

2.6 Entering Basic Settings