Troubleshooting
The connected input/output module is not detected.
Probable Cause
Corrective Action/Description
Reference Page
Module connection or module startup error.
Attached the module while the power was ON.
Turn OFF the power. Detach the input/output module
once and attach it again.
*
The PC software, main module, and input/output
module style and release number rule is not
upheld.
Check the PC software release number and main
module style number before upgrading the version.
[PC software release no.] ≥ [main module style no.] ≥
[input/output module style no.]
**
Carried out an incorrect calibration.
Recalibrate.
4-2
*
See the MW100 Data Acquisition Unit User’s Manual (IM MW100-01E).
**
See the MW100 Data Acquisition Unit Operation Guide (IM MW100-01E).