Energized/De-energized Operation of Output Relays

You can select whether the output relay is energized or de-energized when an output
event (such as an alarm) occurs. If de-energized is selected, the output relay behaves in
the same fashion as when an output event occurs if the power is shut down. The default
setting is Energized. The FAIL output is fixed to De-energized.

NO

Energize

De-energize

C

NO C

NO

C

NO

C

NO C

NO C

When power is

shut down

NO: Normally Opened, C: Common

When alarm is

not occurring

When alarm is

occurring

Hold/Non-Hold of Output Relays

Select the behavior of the output relay when an output event is released (recovers to a
normal condition). The default setting is Non-hold
• Turn OFF the output relay with the release of the output event (non-hold).
• Hold the output relay at ON until the

Relay ACK button (see below) is clicked.

Relay ACK button

Output cause

occurrence

• When set to non-hold

• When set to hold

Relay output ON

Relay output OFF

Relay ACK

Relay output ON

Relay output OFF

Output cause

occurrence

Note

If connection with the PC is dropped, the state at the point at which the DO output was dropped
is retained. However, DO output to which measurement channel alarm detection is assigned
functions normally even if the connection with the PC is dropped.