Mammoth V-Cube Slim Split F-Series Sizes 830 and 840 User Manual

Page 12

Advertising
background image

Mammoth V-Cube Slim Split IOM, MAMM-VCS-IOM-3FA (September 2013) 12

pipe fitting to accommodate the condensate drain con-

nection.
Do not locate any point in the drain system above the

drain connection of any unit.
The condensate piping system must be vented at its

highest point.

Cleaning and Flushing

Before building water is connected to the unit, the build-

ing water system must be flushed clean of particulate

contaminants. Follow the procedures described in this

section.

IMPORTANT! Performance of WSHP units

relies upon a building water supply filtered of

any particulate and chemical contaminants.

Before building water is connected to the unit,

the building water system must be flushed

clean of particulate contaminants. The build-

ing water system is also required to have a

neutral PH balance.
Failure to bring the building water system into

compliance with these requirements, verifi-

able by recorded documentation, will void unit

warranties.

1. Open all air vents.
2. Fill the system at the city water makeup connection.
3. After filling, close all air vents.
4. Open the pressure reducing valve.
5. Check air vents in sequence to bleed off any trapped

air, providing circulation through all components of

the system.

6. Check and repair any leaks in the piping.
7. Start the main circulator with the pressure reducing

valve open.

8. Open the drains at the lowest point(s) in the system

for the initial flush and blow down, making sure city

water fill valves are set to make up water at the same

rate.

9. Check the pressure gauge at the pump suction and

manually adjust the makeup to hold the same posi-

tive steady pressure both before and after opening

the drain valves.

10. Flush the system for at least two hours, or longer if

required, until the drain water is clear and clean.

11. Shut off the supplemental heater (if applicable) and

the circulator pump.

12. Open all drains and vents to completely drain down

the system. .

13. Refill the system with clean water.
14. Test the water using litmus paper for acidity and treat

as required to leave the water slightly alkaline (pH 7.5

to 8.5).

15. The specified percentage of antifreeze may also be

added at this time. Use commercial grade antifreeze

designed for HVAC systems only. Do not use auto-

motive grade antifreeze.

16. Once the system has been filled with clean water and

antifreeze (if used), precaution should be taken to

protect the system from dirty water conditions.

IMPORTANT! Dirty water will result in sys-

tem-wide performance degradation and solids

may clog valves, strainers, flow regulators,

etc. Additionally, the heat exchangers may

become clogged which reduces compressor

service life or causes premature failure.

17. Supply power to all motors and start the circulation

pumps.

18. After full flow has been established through all com-

ponents, including the heat exchanger (regardless of

season), and after air has been vented and loop tem-

peratures stabilized, each of the units will be ready

for check, test, startup, and water balancing.

Electrical Connections

CAUTION! Verify that the unit label voltage

matches building power before connecting

power wires to the unit. Do not apply power to

the unit until all installation work is completed.

Wiring to the unit is routed through the electrical knockout

in the top of the main electrical panel. See . The incoming

power connection is made

at the power voltage termi-

nal block and the ground wire is connected to the unit’s

grounding lug. Control wiring enters the unit through the

small knockout on top of the main electrical panel.

Advertising