Mammoth V-Cube Slim Split IOM, MAMM-VCS-IOM-3FA (September 2013) 13
Figure 13: Electrical Connection Points
Field
control
wiring
Power
wiring
Operating Voltage
Incoming power supply must comply with the data in
Table 1. Unit operation outside of the Min/Max range is
not recommended and will result in premature component
failure.
Table 1: Operating voltages
Minimum
Maximum
208-230/60/3
197 volts
253 volts
460/60/3
414 volts
506 volts
380-415/50/3
342 volts
418 volts
575/60/3
515 volts
632 volts
.
IMPORTANT! Units operating with over- or
under-voltage conditions for extended periods
of time will experience premature component
failure. Three-phase system imbalance should
not exceed 2%.