Mammoth V-Cube Slim Split IOM, MAMM-VCS-IOM-3FA (September 2013) 13

Figure 13: Electrical Connection Points

Field

control

wiring

Power

wiring

Operating Voltage

Incoming power supply must comply with the data in

Table 1. Unit operation outside of the Min/Max range is

not recommended and will result in premature component

failure.
Table 1: Operating voltages

Minimum

Maximum

208-230/60/3

197 volts

253 volts

460/60/3

414 volts

506 volts

380-415/50/3

342 volts

418 volts

575/60/3

515 volts

632 volts

.

IMPORTANT! Units operating with over- or

under-voltage conditions for extended periods

of time will experience premature component

failure. Three-phase system imbalance should

not exceed 2%.