Mammoth V-Cube Slim Split F-Series Sizes 830 and 840 User Manual
Page 7
Mammoth V-Cube Slim Split IOM, MAMM-VCS-IOM-3FA (September 2013) 7
Main Electrical Panel Removal
The main electrical panel is removed as follows.
1. Unplug the wiring harness that connects the EPiC™
keypad, reset buttons and selector switches from the
panel door to the main electrical panel.
2. Remove the panel door by lifting it from its hinges.
Carefully set it away from the unit to help prevent
damage during the remaining disassembly process.
3. Unplug all control wiring harnesses that run from the
main electrical panel to the main cabinet section. All
wiring connecting the main electrical panel to the unit
passes through knockouts on the left inside corner.
These plugs are labeled for correct re-installation.
4. Disconnect all high voltage wiring to the fan motors.
5. Verify that all electrical connections to the unit from
the control panel have been disconnected.
6. Support the electrical panel from above or below to
prevent it from falling once the connecting bolts have
been removed.
7. Loosen and remove the section bolts that fasten the
main electrical panel to the main cabinet sections, as
shown in Figure 3.
8. Set the main electrical panel aside, away from the
unit to help prevent damage during the remaining dis-
assembly process.
Figure 3: Main Electrical Panel Removal
Remove
mounting
bolts
Splitting Apart The Main Sections
To disassemble the unit’s two main sections into separate
halves, carry out the following procedures. To reassem-
ble, follow these procedures in reverse.
1. Remove all access panels and set them aside. See
Figure 4. Quarter turn, twist lock fasteners secure
most access panels.
Figure 4: Panel Removal
Unit Rear
Unit Front
2. Facing the rear side of the unit, loosen the top piping
connections between the two main sections as shown
in Figure 5. The pipes will separate as cabinet halves
are separated.
Figure 5: Rear Side Piping Disconnects
End piping assembly
connections
Top piping
connections
3. Loosen the piping connections on either end of the
end piping assembly, as shown in Figure 5. Then
remove the end piping assembly and set it aside. (If
the end piping assembly is not already installed, it is
packed inside the unit for field assembly.)
4. Facing the front of the unit, loosen the piping connec-
tions between the two main sections as shown in Fig-
ure 6. The pipe connections will separate as cabinet
halves are separated.