Main Electrical Panel Removal

The main electrical panel is removed as follows.
1. Unplug the wiring harness that connects the EPiC™

keypad, reset buttons and selector switches from the

panel door to the main electrical panel.

2. Remove the panel door by lifting it from its hinges.

Carefully set it away from the unit to help prevent

damage during the remaining disassembly process.

3. Unplug all control wiring harnesses that run from the

main electrical panel to the main cabinet section. All

wiring connecting the main electrical panel to the unit

passes through knockouts on the left inside corner.

These plugs are labeled for correct re-installation.

4. Disconnect all high voltage wiring to the fan motors.
5. Verify that all electrical connections to the unit from

the control panel have been disconnected.

6. Support the electrical panel from above or below to

prevent it from falling once the connecting bolts have

been removed.

7. Loosen and remove the section bolts that fasten the

main electrical panel to the main cabinet sections, as

shown in Figure 3.

8. Set the main electrical panel aside, away from the

unit to help prevent damage during the remaining dis-

assembly process.

Figure 3: Main Electrical Panel Removal

Remove

mounting

bolts

Splitting Apart The Main Sections

To disassemble the unit’s two main sections into separate

halves, carry out the following procedures. To reassem-

ble, follow these procedures in reverse.

1. Remove all access panels and set them aside. See

Figure 4. Quarter turn, twist lock fasteners secure

most access panels.

Figure 4: Panel Removal

Unit Rear

Unit Front

2. Facing the rear side of the unit, loosen the top piping

connections between the two main sections as shown

in Figure 5. The pipes will separate as cabinet halves

are separated.

Figure 5: Rear Side Piping Disconnects

End piping assembly

connections

Top piping

connections

3. Loosen the piping connections on either end of the

end piping assembly, as shown in Figure 5. Then

remove the end piping assembly and set it aside. (If

the end piping assembly is not already installed, it is

packed inside the unit for field assembly.)

4. Facing the front of the unit, loosen the piping connec-

tions between the two main sections as shown in Fig-

ure 6. The pipe connections will separate as cabinet

halves are separated.